3 results (0.007 seconds)

CVSS: 6.1EPSS: 0%CPEs: 6EXPL: 0

Sensitive Cookie Without 'HttpOnly' Flag vulnerability in ABB REX640 PCL1 (firmware modules), ABB REX640 PCL2 (Firmware modules), ABB REX640 PCL3 (firmware modules) allows Cross-Site Scripting (XSS).This issue affects REX640 PCL1: from 1.0;0 before 1.0.8; REX640 PCL2: from 1.0;0 before 1.1.4; REX640 PCL3: from 1.0;0 before 1.2.1. • https://search.abb.com/library/Download.aspx?DocumentID=2NGA001423&LanguageCode=en&DocumentPartId=&Action=Launch • CWE-732: Incorrect Permission Assignment for Critical Resource CWE-1004: Sensitive Cookie Without 'HttpOnly' Flag •

CVSS: 6.2EPSS: 0%CPEs: 64EXPL: 0

Improper Initialization vulnerability in ABB Relion protection relays - 611 series, ABB Relion protection relays - 615 series IEC 4.0 FP1, ABB Relion protection relays - 615 series CN 4.0 FP1, ABB Relion protection relays - 615 series IEC 5.0, ABB Relion protection relays - 615 series IEC 5.0 FP1, ABB Relion protection relays - 620 series IEC/CN 2.0, ABB Relion protection relays - 620 series IEC/CN 2.0 FP1, ABB Relion protection relays - REX640 PCL1, ABB Relion protection relays - REX640 PCL2, ABB Relion protection relays - REX640 PCL3, ABB Relion protection relays - RER615, ABB Remote Monitoring and Control - REC615, ABB Merging Unit- SMU615 allows Communication Channel Manipulation.This issue affects Relion protection relays - 611 series: from 1.0.0 before 2.0.3; Relion protection relays - 615 series IEC 4.0 FP1: from 4.1.0 before 4.1.9; Relion protection relays - 615 series CN 4.0 FP1: from 4.1.0 before 4.1.8; Relion protection relays - 615 series IEC 5.0: from 5.0.0 before 5.0.12; Relion protection relays - 615 series IEC 5.0 FP1: from 5.1.0 before 5.1.20; Relion protection relays - 620 series IEC/CN 2.0: from 2.0.0 before 2.0.11; Relion protection relays - 620 series IEC/CN 2.0 FP1: from 2.1.0 before 2.1.15; Relion protection relays - REX640 PCL1: from 1.0.0 before 1.0.8; Relion protection relays - REX640 PCL2: from 1.1.0 before 1.1.4; Relion protection relays - REX640 PCL3: from 1.2.0 before 1.2.1; Relion protection relays - RER615: from 2.0.0 before 2.0.3; Remote Monitoring and Control - REC615: from 1.0.0 before 2.0.3; Merging Unit- SMU615: from 1.0.0 before 1.0.2. • https://search.abb.com/library/Download.aspx?DocumentID=2NGA001147&LanguageCode=en&DocumentPartId=&Action=Launch • CWE-665: Improper Initialization •

CVSS: 6.5EPSS: 0%CPEs: 6EXPL: 0

Incorrect Permission Assignment for Critical Resource vulnerability in ABB REX640 PCL1, REX640 PCL2, REX640 PCL3 allows an authenticated attacker to launch an attack against the user database file and try to take control of an affected system node. Una vulnerabilidad de Asignación incorrecta de permisos para recursos críticos en ABB REX640 PCL1, REX640 PCL2, REX640 PCL3 permite a un atacante autenticado lanzar un ataque contra el archivo de la base de datos del usuario e intentar tomar el control de un nodo del sistema afectado • https://search.abb.com/library/Download.aspx?DocumentID=2NGA001421 • CWE-732: Incorrect Permission Assignment for Critical Resource •