6 results (0.021 seconds)

CVSS: 4.6EPSS: 0%CPEs: 1EXPL: 0

Incorrect Calculation of Buffer Size (CWE-131) in the Controller 6000 and Controller 7000 OSDP message handling, allows an attacker with physical access to Controller wiring to instigate a reboot leading to a denial of service. This issue affects: Controller 6000 and Controller 7000 9.10 prior to vCR9.10.240816a (distributed in 9.10.1530 (MR2)), 9.00 prior to vCR9.00.240816a (distributed in 9.00.2168 (MR4)), 8.90 prior to vCR8.90.240816a (distributed in 8.90.2155 (MR5)), 8.80 prior to vCR8.80.240816b (distributed in 8.80.1938 (MR6)), all versions of 8.70 and prior. • https://security.gallagher.com/en-NZ/Security-Advisories/CVE-2024-39808 • CWE-131: Incorrect Calculation of Buffer Size •

CVSS: 6.5EPSS: 0%CPEs: 1EXPL: 0

Buffer Copy without Checking Size of Input (CWE-120) in the Controller 6000 and Controller 7000 diagnostic web interface allows an authorised and authenticated operator to reboot the Controller, causing a Denial of Service. Gallagher recommend the diagnostic web page is not enabled (default is off) unless advised by Gallagher Technical support. This interface is intended only for diagnostic purposes. This issue affects: Controller 6000 and Controller 7000 9.10 prior to vCR9.10.240816a (distributed in 9.10.1530 (MR2)), 9.00 prior to vCR9.00.240816a (distributed in 9.00.2168 (MR4)), 8.90 prior to vCR8.90.240816a (distributed in 8.90.2155 (MR5)), 8.80 prior to vCR8.80.240816b (distributed in 8.80.1938 (MR6)), all versions of 8.70 and prior. • https://security.gallagher.com/en-NZ/Security-Advisories/CVE-2024-24972 • CWE-120: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') •

CVSS: 6.1EPSS: 0%CPEs: 1EXPL: 0

Improper Neutralization of Input During Web Page Generation (CWE-79) in the Controller 6000 and Controller 7000 diagnostic webpage allows an attacker to modify Controller configuration during an authenticated Operator's session. This issue affects: Controller 6000 and Controller 7000 9.10 prior to vCR9.10.240816a (distributed in 9.10.1530 (MR2)), 9.00 prior to vCR9.00.240816a (distributed in 9.00.2168 (MR4)), 8.90 prior to vCR8.90.240816a (distributed in 8.90.2155 (MR5)), 8.80 prior to vCR8.80.240816b (distributed in 8.80.1938 (MR6)), all versions of 8.70 and prior. • https://security.gallagher.com/en-NZ/Security-Advisories/CVE-2024-23906 • CWE-79: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') •

CVSS: 6.3EPSS: 0%CPEs: 1EXPL: 0

External Control of File Name or Path (CWE-73) in the Controller 6000 and Controller 7000 allows an attacker with local access to the Controller to perform arbitrary code execution. This issue affects: 9.10 prior to vCR9.10.240520a (distributed in 9.10.1268(MR1)), 9.00 prior to vCR9.00.240521a (distributed in 9.00.1990(MR3)), 8.90 prior to vCR8.90.240520a (distributed in 8.90.1947 (MR4)), 8.80 prior to vCR8.80.240520a (distributed in 8.80.1726 (MR5)), 8.70 prior to vCR8.70.240520a (distributed in 8.70.2824 (MR7)), all versions of 8.60 and prior. El control externo del nombre o ruta del archivo (CWE-73) en el Controlador 6000 y el Controlador 7000 permite a un atacante con acceso local al Controlador realizar la ejecución de código arbitrario. Este problema afecta a: 9.10 anterior a vCR9.10.240520a (distribuido en 9.10.1268(MR1)), 9.00 anterior a vCR9.00.240521a (distribuido en 9.00.1990(MR3)), 8.90 anterior a vCR8.90.240520a (distribuido en 8.90.1947 (MR4)), 8.80 antes de vCR8.80.240520a (distribuido en 8.80.1726 (MR5)), 8.70 antes de vCR8.70.240520a (distribuido en 8.70.2824 (MR7)), todas las versiones de 8.60 y anteriores . • https://security.gallagher.com/Security-Advisories/CVE-2024-23317 • CWE-73: External Control of File Name or Path •

CVSS: 6.8EPSS: 0%CPEs: 1EXPL: 0

External Control of Critical State Data (CWE-642) in the Controller 6000 and Controller 7000 diagnostic web interface allows an authenticated user to modify device I/O connections leading to unexpected behavior that in some circumstances could compromise site physical security controls. Gallagher recommend the diagnostic web page is not enabled (default is off) unless advised by Gallagher Technical support. This interface is intended only for diagnostic purposes. This issue affects: Gallagher Controller 6000 and 7000 9.10 prior to vCR9.10.240520a (distributed in 9.10.1268(MR1)), 9.00 prior to vCR9.00.240521a (distributed in 9.00.1990(MR3)), 8.90 prior to vCR8.90.240520a (distributed in 8.90.1947 (MR4)), 8.80 prior to vCR8.80.240520a (distributed in 8.80.1726 (MR5)), 8.70 prior to vCR8.70.240520a (distributed in 8.70.2824 (MR7)), all versions of 8.60 and prior. El control externo de datos de estado crítico (CWE-642) en la interfaz web de diagnóstico del Controlador 6000 y del Controlador 7000 permite a un usuario autenticado modificar las conexiones de E/S del dispositivo, lo que genera un comportamiento inesperado que, en algunas circunstancias, podría comprometer los controles de seguridad física del sitio. Gallagher recomienda que la página web de diagnóstico no esté habilitada (la opción predeterminada está desactivada) a menos que así lo indique el soporte técnico de Gallagher. • https://security.gallagher.com/Security-Advisories/CVE-2024-22387 • CWE-642: External Control of Critical State Data •