9 results (0.009 seconds)

CVSS: 7.8EPSS: 0%CPEs: 74EXPL: 0

21 Feb 2023 — A vulnerability exists in the IEC 61850 communication stack that affects multiple Hitachi Energy products. An attacker could exploit the vulnerability by using a specially crafted message sequence, to force the IEC 61850 MMS-server communication stack, to stop accepting new MMS-client connections. Already existing/established client-server connections are not affected. List of affected CPEs: * cpe:2.3:o:hitachienergy:fox61x_tego1:r15b08:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r2a16_3:*:*:*:*:*:... • https://search.abb.com/library/Download.aspx?DocumentID=8DBD000124&LanguageCode=en&DocumentPartId=&Action=Launch • CWE-404: Improper Resource Shutdown or Release •

CVSS: 8.8EPSS: 0%CPEs: 13EXPL: 0

21 Nov 2022 — An input validation vulnerability exists in the Monitor Pro interface of MicroSCADA Pro and MicroSCADA X SYS600. An authenticated user can launch an administrator level remote code execution irrespective of the authenticated user's role. Existe una vulnerabilidad de validación de entrada en la interfaz Monitor Pro de MicroSCADA Pro y MicroSCADA X SYS600. Un usuario autenticado puede iniciar una ejecución remota de código a nivel de administrador independientemente de la función del usuario autenticado. An i... • https://search.abb.com/library/Download.aspx?DocumentID=8DBD000123&LanguageCode=en&DocumentPartId=&Action=Launch&elqaid=4293&elqat=1 • CWE-20: Improper Input Validation •

CVSS: 7.8EPSS: 0%CPEs: 2EXPL: 0

14 Sep 2022 — Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version... • https://search.abb.com/library/Download.aspx?DocumentID=8DBD000106&LanguageCode=en&DocumentPartId=&Action=Launch • CWE-20: Improper Input Validation •

CVSS: 7.5EPSS: 0%CPEs: 2EXPL: 0

14 Sep 2022 — Improper Input Validation vulnerability in Hitachi Energy MicroSCADA X SYS600 while reading a specific configuration file causes a buffer-overflow that causes a failure to start the SYS600. The configuration file can only be accessed by an administrator access. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys6... • https://search.abb.com/library/Download.aspx?DocumentID=8DBD000106&LanguageCode=en&DocumentPartId=&Action=Launch • CWE-20: Improper Input Validation CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer •

CVSS: 7.8EPSS: 0%CPEs: 2EXPL: 0

14 Sep 2022 — Improper Input Validation vulnerability in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. The vulnerability may cause a denial-of-service on the IEC 61850 OPC Server part of the SYS600 product. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1... • https://search.abb.com/library/Download.aspx?DocumentID=8DBD000106&LanguageCode=en&DocumentPartId=&Action=Launch • CWE-20: Improper Input Validation •

CVSS: 7.8EPSS: 0%CPEs: 2EXPL: 0

14 Sep 2022 — Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future to any remote ICCP system. By default, ICCP is not configured and not enabled. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10.2 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:... • https://search.abb.com/library/Download.aspx?DocumentID=8DBD000106&LanguageCode=en&DocumentPartId=&Action=Launch • CWE-20: Improper Input Validation CWE-1284: Improper Validation of Specified Quantity in Input •

CVSS: 9.0EPSS: 0%CPEs: 2EXPL: 0

12 Sep 2022 — Improper Authorization vulnerability exists in the Workplace X WebUI of the Hitachi Energy MicroSCADA X SYS600 allows an authenticated user to execute any MicroSCADA internal scripts irrespective of the authenticated user's role. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:... • https://search.abb.com/library/Download.aspx?DocumentID=8DBD000106&LanguageCode=en&DocumentPartId=&Action=Launch • CWE-285: Improper Authorization •

CVSS: 9.8EPSS: 72%CPEs: 3EXPL: 0

29 Apr 2020 — ABB MicroSCADA Pro SYS600 version 9.3 suffers from an instance of CWE-306: Missing Authentication for Critical Function. ABB MicroSCADA Pro SYS600 versión 9.3, sufre de una instancia CWE-306: Falta de Autenticación para una Función Crítica. • https://www.rapid7.com/db/modules/exploit/windows/scada/abb_wserver_exec • CWE-306: Missing Authentication for Critical Function •

CVSS: 7.8EPSS: 0%CPEs: 6EXPL: 0

06 Feb 2018 — This vulnerability allows local attackers to escalate privileges on vulnerable installations of ABB MicroSCADA 9.3 with FP 1-2-3. An attacker must first obtain the ability to execute low-privileged code on the target system in order to exploit this vulnerability. The specific flaw exists within the configuration of the access controls for the installed product files. The installation procedure leaves critical files open to manipulation by any authenticated user. An attacker can leverage this vulnerability t... • https://library.e.abb.com/public/7a88a74b12bb492ea138b1f2365d00f6/ABBVU-PGGA-33888_ABB_SoftwareVulnerabilityHandlingAdvisory_Rev_A.pdf?x-sign=MJfu9cHtRUUubpLAYzyWFTmW5W+mg3kZ/nm7F/Jw5HlFTQf4eNyfLAgE8HozRJEC • CWE-284: Improper Access Control CWE-732: Incorrect Permission Assignment for Critical Resource •