5 results (0.015 seconds)

CVSS: 7.5EPSS: 0%CPEs: 1EXPL: 0

The affected product is vulnerable to an information leak, which may allow an attacker to obtain sensitive information on the Ignition 8 (all versions prior to 8.0.13). El producto afectado es vulnerable a una filtración de información, lo que puede permitir a un atacante obtener información confidencial en el Ignition 8 (todas las versiones anteriores a 8.0.13) • https://us-cert.cisa.gov/ics/advisories/icsa-20-212-01 • CWE-862: Missing Authorization •

CVSS: 9.8EPSS: 5%CPEs: 2EXPL: 0

The affected product is vulnerable to the handling of serialized data. The issue results from the lack of proper validation of user-supplied data, which can result in deserialization of untrusted data on the Ignition 8 Gateway (versions prior to 8.0.10) and Ignition 7 Gateway (versions prior to 7.9.14), allowing an attacker to obtain sensitive information. El producto afectado es vulnerable al manejo de datos serializados. El problema resulta de la falta de una comprobación apropiada de los datos suministrados por el usuario, lo que puede resultar en una deserialización de datos no confiables en Ignition 8 Gateway (versiones anteriores a 8.0.10) y Ignition 7 Gateway (versiones anteriores a la 7.9.14), permitiendo a un atacante obtener información confidencial This vulnerability allows remote attackers to execute arbitrary code on affected installations of Inductive Automation Ignition. Authentication is not required to exploit this vulnerability. The specific flaw exists with the handling of serialized data. • https://www.us-cert.gov/ics/advisories/icsa-20-147-01 • CWE-502: Deserialization of Untrusted Data •

CVSS: 9.8EPSS: 82%CPEs: 2EXPL: 0

The affected product lacks proper validation of user-supplied data, which can result in deserialization of untrusted data on the Ignition 8 Gateway (versions prior to 8.0.10) and Ignition 7 Gateway (versions prior to 7.9.14), allowing an attacker to obtain sensitive information. El producto afectado carece de una comprobación apropiada de los datos suministrados por el usuario, lo que puede dar resultar en una deserialización de datos no confiables en Ignition 8 Gateway (versiones anteriores a 8.0.10) y Ignition 7 Gateway (versiones anteriores a la 7.9.14), permitiendo a un atacante obtener información confidencial This vulnerability allows remote attackers to execute arbitrary code on affected installations of Inductive Automation Ignition. Authentication is not required to exploit this vulnerability. The specific flaw exists with the handling of project diffs. The issue results from the lack of proper validation of user-supplied data, which can result in deserialization of untrusted data. An attacker can leverage this to execute code in the context of SYSTEM. • http://packetstormsecurity.com/files/158226/Inductive-Automation-Ignition-Remote-Code-Execution.html https://www.us-cert.gov/ics/advisories/icsa-20-147-01 • CWE-502: Deserialization of Untrusted Data •

CVSS: 7.5EPSS: 84%CPEs: 2EXPL: 0

The affected product lacks proper authentication required to query the server on the Ignition 8 Gateway (versions prior to 8.0.10) and Ignition 7 Gateway (versions prior to 7.9.14), allowing an attacker to obtain sensitive information. El producto afectado carece de una autenticación apropiada requerida para consultar el servidor en Ignition 8 Gateway (versiones anteriores a 8.0.10) y Ignition 7 Gateway (versiones anteriores a la 7.9.14), permitiendo a un atacante obtener información confidencial This vulnerability allows remote attackers to disclose sensitive information on affected installations of Inductive Automation Ignition. Authentication is not required to exploit this vulnerability. The specific flaw exists within the getDiffs method of the com.inductiveautomation.ignition.gateway.servlets.gateway.functions.ProjectDownload class. The issue results from the lack of proper authentication required to query to server. An attacker can leverage this in conjunction with other vulnerabilities to execute code in the context of SYSTEM. • http://packetstormsecurity.com/files/158226/Inductive-Automation-Ignition-Remote-Code-Execution.html https://www.us-cert.gov/ics/advisories/icsa-20-147-01 • CWE-306: Missing Authentication for Critical Function •

CVSS: 7.5EPSS: 0%CPEs: 1EXPL: 0

An unprotected logging route may allow an attacker to write endless log statements into the database without space limits or authentication. This results in consuming the entire available hard-disk space on the Ignition 8 Gateway (versions prior to 8.0.10), causing a denial-of-service condition. Una ruta de registro no protegida puede permitir a un atacante escribir sentencias de registro interminables en la base de datos sin límites de espacio o autenticación. Esto resulta en consumir todo el espacio disponible en el disco duro en el Ignition 8 Gateway (versiones anteriores a 8.0.10), causando una condición de denegación de servicio. • https://www.us-cert.gov/ics/advisories/icsa-20-112-01 • CWE-284: Improper Access Control CWE-306: Missing Authentication for Critical Function •