CVE-2024-6207
https://notcve.org/view.php?id=CVE-2024-6207
14 Oct 2024 — CVE 2021-22681 https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1550.html and send a specially crafted CIP message to the device. If exploited, a threat actor could help prevent access to the legitimate user and end connections to connected devices including the workstation. To recover the controllers, a download is required which ends any process that the controller is running. • https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1707.html • CWE-20: Improper Input Validation •

CVE-2022-3157 – Rockwell Automation GuardLogix and ControlLogix controllers Vulnerable to Denial-Of-Service Attack
https://notcve.org/view.php?id=CVE-2022-3157
16 Dec 2022 — A vulnerability exists in the Rockwell Automation controllers that allows a malformed CIP request to cause a major non-recoverable fault (MNRF) and a denial-of-service condition (DOS). Existe una vulnerabilidad en los controladores de Rockwell Automation que permite que una solicitud CIP con formato incorrecto cause una falla mayor no recuperable (MNRF) y una condición de Denegación de Servicio (DoS) (DOS). • https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1137757 • CWE-20: Improper Input Validation •

CVE-2020-6998 – Rockwell Automation CompactLogix 5370 and ControlLogix 5570 Controllers Improper Input Validation
https://notcve.org/view.php?id=CVE-2020-6998
27 Jul 2022 — The connection establishment algorithm found in Rockwell Automation CompactLogix 5370 and ControlLogix 5570 versions 33 and prior does not sufficiently manage its control flow during execution, creating an infinite loop. This may allow an attacker to send specially crafted CIP packet requests to a controller, which may cause denial-of-service conditions in communications with other products. El algoritmo de establecimiento de conexión encontrado en Rockwell Automation CompactLogix 5370 and ControlLogix 5570... • https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1130398 • CWE-20: Improper Input Validation •

CVE-2022-1797 – Rockwell Automation Logix Controllers Uncontrolled Resource Consumption
https://notcve.org/view.php?id=CVE-2022-1797
31 May 2022 — A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online. Un mensaje de protocolo industrial común de clase 3 malformado con una conexión en caché puede causar una condición de denegación de servicio en los controlad... • https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1135559 • CWE-400: Uncontrolled Resource Consumption •

CVE-2022-1161 – ICSA-22-090-05 Rockwell Automation Logix Controllers
https://notcve.org/view.php?id=CVE-2022-1161
11 Apr 2022 — An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other. Un atacante con la capacidad de modificar un programa de usuario puede cambiar el código del programa de usuario en algunos sistemas ControlLogix, CompactLogix y GuardLogix Control. Studio 5... • https://www.cisa.gov/uscert/ics/advisories/icsa-22-090-05 • CWE-829: Inclusion of Functionality from Untrusted Control Sphere •

CVE-2019-10952 – Rockwell Automation CompactLogix 5370 Uncontrolled Resource Consumption
https://notcve.org/view.php?id=CVE-2019-10952
01 May 2019 — An attacker could send a crafted HTTP/HTTPS request to render the web server unavailable and/or lead to remote code execution caused by a stack-based buffer overflow vulnerability. A cold restart is required for recovering CompactLogix 5370 L1, L2, and L3 Controllers, Compact GuardLogix 5370 controllers, and Armor Compact GuardLogix 5370 Controllers Versions 20 - 30 and earlier. Un atacante podría enviar una petición HTTP/HTTPS creada para hacer que el servidor web no esté disponible y/o provocar una ejecuc... • http://www.securityfocus.com/bid/108118 • CWE-400: Uncontrolled Resource Consumption CWE-787: Out-of-bounds Write •

CVE-2019-10954 – Rockwell Automation CompactLogix 5370 Stack-based Buffer Overflow
https://notcve.org/view.php?id=CVE-2019-10954
01 May 2019 — An attacker could send crafted SMTP packets to cause a denial-of-service condition where the controller enters a major non-recoverable faulted state (MNRF) in CompactLogix 5370 L1, L2, and L3 Controllers, Compact GuardLogix 5370 controllers, and Armor Compact GuardLogix 5370 Controllers Versions 20 - 30 and earlier. Un atacante podría enviar paquetes SMTP creados para causar una condición de denegación de servicio en la que el controlador entra en un estado de fallo superior no recuperable (MNRF) en los con... • http://www.securityfocus.com/bid/108118 • CWE-121: Stack-based Buffer Overflow CWE-787: Out-of-bounds Write •

CVE-2016-9343
https://notcve.org/view.php?id=CVE-2016-9343
13 Feb 2017 — An issue was discovered in Rockwell Automation Logix5000 Programmable Automation Controller FRN 16.00 through 21.00 (excluding all firmware versions prior to FRN 16.00, which are not affected). By sending malformed common industrial protocol (CIP) packet, an attacker may be able to overflow a stack-based buffer and execute code on the controller or initiate a nonrecoverable fault resulting in a denial of service. Ha sido descubierto un problema en Rockwell Automation Logix5000 Programmable Automation Contro... • http://www.securityfocus.com/bid/95304 • CWE-787: Out-of-bounds Write •