4 results (0.012 seconds)

CVSS: 5.3EPSS: 0%CPEs: 62EXPL: 0

A CWE-117: Improper Output Neutralization for Logs vulnerability exists that could cause the misinterpretation of log files when malicious packets are sent to the Geo SCADA server's database web port (default 443). Affected products: EcoStruxure Geo SCADA Expert 2019, EcoStruxure Geo SCADA Expert 2020, EcoStruxure Geo SCADA Expert 2021(All Versions prior to October 2022), ClearSCADA (All Versions) • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-045-01&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2023-045-01.pdf • CWE-116: Improper Encoding or Escaping of Output CWE-117: Improper Output Neutralization for Logs •

CVSS: 7.5EPSS: 0%CPEs: 61EXPL: 0

A CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exists that could cause information disclosure when specific messages are sent to the server over the database server TCP port. Affected Products: EcoStruxure Geo SCADA Expert 2019 - 2021 (formerly known as ClearSCADA) (Versions prior to October 2022) Existe una vulnerabilidad CWE-200: Exposición de información confidencial a un actor no autorizado que podría provocar la divulgación de información cuando se envían mensajes específicos al servidor a través del puerto TCP del servidor de la base de datos. Productos afectados: EcoStruxure Geo SCADA Expert 2019 - 2021 (anteriormente conocido como ClearSCADA) (Versiones anteriores a octubre de 2022) • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-010-02&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2023-010-02_Geo_SCADA_Security_Notification.pdf • CWE-200: Exposure of Sensitive Information to an Unauthorized Actor •

CVSS: 9.1EPSS: 0%CPEs: 61EXPL: 0

A CWE-863: Incorrect Authorization vulnerability exists that could cause Denial of Service against the Geo SCADA server when specific messages are sent to the server over the database server TCP port. • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-010-02&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2023-010-02_Geo_SCADA_Security_Notification.pdf • CWE-863: Incorrect Authorization •

CVSS: 7.8EPSS: 0%CPEs: 2EXPL: 0

A CWE-522: Insufficiently Protected Credentials vulnerability exists in EcoStruxure Geo SCADA Expert 2019 (Original release and Monthly Updates to September 2020, from 81.7268.1 to 81.7578.1) and EcoStruxure Geo SCADA Expert 2020 (Original release and Monthly Updates to September 2020, from 83.7551.1 to 83.7578.1), that could cause exposure of credentials to server-side users when web users are logged in to Virtual ViewX. Una CWE-522: Se presenta una vulnerabilidad de Credenciales Insuficientemente Protegidas en EcoStruxure Geo SCADA Expert 2019 (versión original y Actualizaciones Mensuales hasta Septiembre de 2020, desde 81.7268.1 hasta 81.7578.1) y EcoStruxure Geo SCADA Expert 2020 (versión original y Actualizaciones Mensuales hasta Septiembre de 2020), desde 83.7551.1 hasta 83.7578.1), que podría causar la exposición de las credenciales a los usuarios del lado del servidor cuando los usuarios web inician sesión en Virtual ViewX • https://www.se.com/ww/en/download/document/SEVD-2020-343-02 • CWE-522: Insufficiently Protected Credentials •