17 results (0.012 seconds)

CVSS: 8.5EPSS: 0%CPEs: 1EXPL: 0

13 Feb 2025 — CWE-269: Improper Privilege Management vulnerability exists for two services (of which one managing audit trail data and the other acting as server managing client request) that could cause a loss of Confidentiality, Integrity and Availability of engineering workstation when an attacker with standard privilege modifies the executable path of the windows services. To be exploited, services need to be restarted. CWE-269: Improper Privilege Management vulnerability exists for two services (of which one managin... • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-042-03&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2025-042-03.pdf • CWE-269: Improper Privilege Management •

CVSS: 6.8EPSS: 0%CPEs: 5EXPL: 0

13 Feb 2025 — CWE-20: Improper Input Validation vulnerability exists that could cause denial of service of engineering workstation when specific driver interface is invoked locally by an authenticated user with crafted input. CWE-20: Improper Input Validation vulnerability exists that could cause denial of service of engineering workstation when specific driver interface is invoked locally by an authenticated user with crafted input. • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-042-02&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2025-042-02.pdf • CWE-20: Improper Input Validation •

CVSS: 10.0EPSS: 0%CPEs: 72EXPL: 0

31 Jan 2023 — A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause execution of unauthorized Modbus functions on the controller when hijacking an authenticated Modbus session. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions) • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-010-06&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2023-010-06_Modicon_Controllers_Security_Notification.pdf • CWE-294: Authentication Bypass by Capture-replay •

CVSS: 10.0EPSS: 0%CPEs: 108EXPL: 0

30 Jan 2023 — A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when a malicious project file is loaded onto the controller. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers B... • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-010-05&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2023-010-05_Modicon_Controllers_Security_Notification.pdf • CWE-754: Improper Check for Unusual or Exceptional Conditions •

CVSS: 10.0EPSS: 0%CPEs: 70EXPL: 0

12 Sep 2022 — A CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists that could cause unauthorized access in read and write mode to the controller when communicating over Modbus. Affected Products: EcoStruxure Control Expert Including all Unity Pro versions (former name of EcoStruxure Control Expert) (V15.0 SP1 and prior), EcoStruxure Process Expert, Including all versions of EcoStruxure Hybrid DCS (former name of EcoStruxure Process Expert) (V2021 and prior), Modicon M340 CPU (part numbe... • https://www.se.com/us/en/download/document/SEVD-2022-221-01 • CWE-640: Weak Password Recovery Mechanism for Forgotten Password •

CVSS: 9.8EPSS: 3%CPEs: 10EXPL: 0

14 Apr 2022 — A heap-based buffer overflow exists in XML Decompression DecodeTreeBlock in AT&T Labs Xmill 0.7. A crafted input file can lead to remote code execution. This is not the same as any of: CVE-2021-21810, CVE-2021-21811, CVE-2021-21812, CVE-2021-21815, CVE-2021-21825, CVE-2021-21826, CVE-2021-21828, CVE-2021-21829, or CVE-2021-21830. NOTE: This vulnerability only affects products that are no longer supported by the maintainer Se presenta un desbordamiento de búfer en la región heap de la memoria en XML Decompre... • https://Claroty.com • CWE-787: Out-of-bounds Write •

CVSS: 5.9EPSS: 0%CPEs: 4EXPL: 0

09 Mar 2022 — A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause a disruption of communication between the Modicon controller and the engineering software, when an attacker is able to intercept and manipulate specific Modbus response data. Affected Product: EcoStruxure Process Expert (V2021 and prior), EcoStruxure Control Expert (V15.0 SP1 and prior) Una CWE-754: Se presenta una vulnerabilidad de Comprobación Inapropiada de Condiciones no Usuales o Excepcionales que podr... • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-067-01 • CWE-754: Improper Check for Unusual or Exceptional Conditions •

CVSS: 9.3EPSS: 0%CPEs: 8EXPL: 0

20 Sep 2021 — A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal) vulnerability exists that could cause malicious script to be deployed in an unauthorized location and may result in code execution on the engineering workstation when a malicious project file is loaded in the engineering software. Affected Product: EcoStruxure Control Expert (V15.0 SP1 and prior, including former Unity Pro), EcoStruxure Process Expert (2020 and prior, including former HDCS), SCADAPack RemoteConnect for x... • https://www.se.com/ww/en/download/document/SEVD-2021-257-01 • CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') •

CVSS: 7.5EPSS: 0%CPEs: 49EXPL: 0

02 Sep 2021 — A CWE-476: NULL Pointer Dereference vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including ... • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-222-04 • CWE-476: NULL Pointer Dereference •

CVSS: 6.5EPSS: 0%CPEs: 49EXPL: 0

02 Sep 2021 — A CWE-787: Out-of-bounds Write vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all U... • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-222-04 • CWE-787: Out-of-bounds Write •