4 results (0.002 seconds)

CVSS: 7.8EPSS: 0%CPEs: 24EXPL: 0

A CWE-119:Improper restriction of operations within the bounds of a memory buffer vulnerability exists in PowerLogic ION8650, ION8800, ION7650, ION7700/73xx, and ION83xx/84xx/85xx/8600 (see security notifcation for affected versions), which could cause the meter to reboot. A CWE-119: se presenta vulnerabilidad de Restricción Inapropiada de Operaciones dentro de los Límites de un Búfer de la Memoria en PowerLogic ION8650, ION8800, ION7650, ION7700 /73xx e ION83xx /84xx/85xx /8600 (consulte la notificación de seguridad para las versiones afectadas), lo que podría causar al medidor reiniciarse • https://www.se.com/ww/en/download/document/SEVD-2021-068-03 • CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer •

CVSS: 7.5EPSS: 0%CPEs: 24EXPL: 0

A CWE-319: Cleartext transmission of sensitive information vulnerability exists in PowerLogic ION7400, ION7650, ION7700/73xx, ION83xx/84xx/85xx/8600, ION8650, ION8800, ION9000 and PM800 (see notification for affected versions), that could cause disclosure of user credentials when a malicious actor intercepts Telnet network traffic between a user and the device. A CWE-319: Se presenta una vulnerabilidad de transmisión de información confidencial en texto sin cifrar en PowerLogic ION7400, ION7650, ION7700/73xx, ION83xx/84xx/85xx/8600, ION8650, ION8800, ION9000 y PM800 (consulte la notificación para las versiones afectadas), que podría causar una divulgación de credenciales de usuario cuando un actor malicioso intercepta el tráfico de red Telnet entre un usuario y el dispositivo • https://www.se.com/ww/en/download/document/SEVD-2021-040-01 • CWE-319: Cleartext Transmission of Sensitive Information •

CVSS: 9.8EPSS: 0%CPEs: 6EXPL: 0

An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. No authentication is configured by default. An unauthorized user can access the device management portal and make configuration changes. Ha sido descubierto un problema en los medidores de potencia de las series IONXXXX, ION73XX, ION75XX, ION76XX, ION8650, ION8800 y PM5XXX de Schneider Electric. Ninguna autenticación está configurada de forma predeterminada. • http://www.securityfocus.com/bid/94091 https://ics-cert.us-cert.gov/advisories/ICSA-16-308-03 • CWE-284: Improper Access Control •

CVSS: 8.8EPSS: 0%CPEs: 6EXPL: 1

An issue was discovered on Schneider Electric IONXXXX series power meters ION73XX series, ION75XX series, ION76XX series, ION8650 series, ION8800 series, and PM5XXX series. There is no CSRF Token generated to authenticate the user during a session. Successful exploitation of this vulnerability can allow unauthorized configuration changes to be made and saved. Ha sido descubierto un problema en los medidores de potencia de las series IONXXXX, ION73XX, ION75XX, ION76XX, ION8650, ION8800 y PM5XXX de Schneider Electric. No hay Token CSRF generado para autenticar al usuario durante una sesión. • https://www.exploit-db.com/exploits/44640 http://www.securityfocus.com/bid/92916 https://ics-cert.us-cert.gov/advisories/ICSA-16-308-03 • CWE-352: Cross-Site Request Forgery (CSRF) •