CVE-2021-22786
https://notcve.org/view.php?id=CVE-2021-22786
01 Feb 2023 — A CWE-200: Information Exposure vulnerability exists that could cause the exposure of sensitive information stored on the memory of the controller when communicating over the Modbus TCP protocol. Affected Products: Modicon M340 CPU (part numbers BMXP34*) (Versions prior to V3.30), Modicon M580 CPU (part numbers BMEP* and BMEH*) (Versions prior to SV3.20), Modicon MC80 (BMKC80) (Versions prior to V1.6), Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S) (All Versions), Modicon Momentum MDI (171CBU*... • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-221-04&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2022-221-04-Modicon_Controllers_Ethernet_Modules_Security_Notification.pdf • CWE-200: Exposure of Sensitive Information to an Unauthorized Actor •

CVE-2022-45789
https://notcve.org/view.php?id=CVE-2022-45789
31 Jan 2023 — A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause execution of unauthorized Modbus functions on the controller when hijacking an authenticated Modbus session. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions) • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-010-06&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2023-010-06_Modicon_Controllers_Security_Notification.pdf • CWE-294: Authentication Bypass by Capture-replay •

CVE-2022-45788
https://notcve.org/view.php?id=CVE-2022-45788
30 Jan 2023 — A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when a malicious project file is loaded onto the controller. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers B... • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-010-05&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2023-010-05_Modicon_Controllers_Security_Notification.pdf • CWE-754: Improper Check for Unusual or Exceptional Conditions •

CVE-2022-0222
https://notcve.org/view.php?id=CVE-2022-0222
22 Nov 2022 — A CWE-269: Improper Privilege Management vulnerability exists that could cause a denial of service of the Ethernet communication of the controller when sending a specific request over SNMP. Affected products: Modicon M340 CPUs(BMXP34* versions prior to V3.40), Modicon M340 X80 Ethernet Communication modules:BMXNOE0100 (H), BMXNOE0110 (H), BMXNOR0200H RTU(BMXNOE* all versions)(BMXNOR* versions prior to v1.7 IR24) Existe una vulnerabilidad CWE-269: Gestión de privilegios inadecuada que podría provocar una Den... • https://www.se.com/us/en/download/document/SEVD-2022-102-02 • CWE-269: Improper Privilege Management •

CVE-2022-37300
https://notcve.org/view.php?id=CVE-2022-37300
12 Sep 2022 — A CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists that could cause unauthorized access in read and write mode to the controller when communicating over Modbus. Affected Products: EcoStruxure Control Expert Including all Unity Pro versions (former name of EcoStruxure Control Expert) (V15.0 SP1 and prior), EcoStruxure Process Expert, Including all versions of EcoStruxure Hybrid DCS (former name of EcoStruxure Process Expert) (V2021 and prior), Modicon M340 CPU (part numbe... • https://www.se.com/us/en/download/document/SEVD-2022-221-01 • CWE-640: Weak Password Recovery Mechanism for Forgotten Password •

CVE-2022-22724
https://notcve.org/view.php?id=CVE-2022-22724
04 Feb 2022 — A CWE-400: Uncontrolled Resource Consumption vulnerability exists that could cause a denial of service on ports 80 (HTTP) and 502 (Modbus), when sending a large number of TCP RST or FIN packets to any open TCP port of the PLC. Affected Product: Modicon M340 CPUs: BMXP34 (All Versions) Una CWE-400: Se presenta una vulnerabilidad de Consumo no Controlado de Recursos que podría causar una denegación de servicio en los puertos 80 (HTTP) y 502 (Modbus), cuando es enviado un gran número de paquetes TCP RST o FIN ... • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-011-01 • CWE-400: Uncontrolled Resource Consumption •

CVE-2021-22792
https://notcve.org/view.php?id=CVE-2021-22792
02 Sep 2021 — A CWE-476: NULL Pointer Dereference vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including ... • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-222-04 • CWE-476: NULL Pointer Dereference •

CVE-2021-22791
https://notcve.org/view.php?id=CVE-2021-22791
02 Sep 2021 — A CWE-787: Out-of-bounds Write vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all U... • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-222-04 • CWE-787: Out-of-bounds Write •

CVE-2021-22790
https://notcve.org/view.php?id=CVE-2021-22790
02 Sep 2021 — A CWE-125: Out-of-bounds Read vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Un... • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-222-04 • CWE-125: Out-of-bounds Read •

CVE-2021-22789
https://notcve.org/view.php?id=CVE-2021-22789
02 Sep 2021 — A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simula... • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-222-04 • CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer •