9 results (0.004 seconds)

CVSS: 7.5EPSS: 0%CPEs: 82EXPL: 0

A CWE-200: Information Exposure vulnerability exists that could cause the exposure of sensitive information stored on the memory of the controller when communicating over the Modbus TCP protocol. Affected Products: Modicon M340 CPU (part numbers BMXP34*) (Versions prior to V3.30), Modicon M580 CPU (part numbers BMEP* and BMEH*) (Versions prior to SV3.20), Modicon MC80 (BMKC80) (Versions prior to V1.6), Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S) (All Versions), Modicon Momentum MDI (171CBU*) (Versions prior to V2.3), Legacy Modicon Quantum (All Versions) • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-221-04&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2022-221-04-Modicon_Controllers_Ethernet_Modules_Security_Notification.pdf • CWE-200: Exposure of Sensitive Information to an Unauthorized Actor •

CVSS: 9.8EPSS: 0%CPEs: 72EXPL: 0

A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause execution of unauthorized Modbus functions on the controller when hijacking an authenticated Modbus session. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions) • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-010-06&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2023-010-06_Modicon_Controllers_Security_Notification.pdf • CWE-294: Authentication Bypass by Capture-replay •

CVSS: 9.8EPSS: 0%CPEs: 108EXPL: 0

A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when a malicious project file is loaded onto the controller. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions), Modicon Momentum Unity M1E Processor - 171CBU* (All Versions), Modicon MC80 - BMKC80 (All Versions), Legacy Modicon Quantum - 140CPU65* and Premium CPUs - TSXP57* (All Versions) • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-010-05&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2023-010-05_Modicon_Controllers_Security_Notification.pdf • CWE-754: Improper Check for Unusual or Exceptional Conditions •

CVSS: 7.5EPSS: 0%CPEs: 96EXPL: 0

A CWE-191: Integer Underflow (Wrap or Wraparound) vulnerability exists that could cause a denial of service of the controller due to memory access violations when using the Modbus TCP protocol. Affected products: Modicon M340 CPU (part numbers BMXP34*)(V3.40 and prior), Modicon M580 CPU (part numbers BMEP* and BMEH*)(V3.22 and prior), Legacy Modicon Quantum/Premium(All Versions), Modicon Momentum MDI (171CBU*)(All Versions), Modicon MC80 (BMKC80)(V1.7 and prior) Existe una vulnerabilidad CWE-191: Integer Underflow (Wrap o Wraparound) que podría causar una Denegación de Servicio (DoS) del controlador debido a violaciones de acceso a la memoria cuando se utiliza el protocolo Modbus TCP. Productos afectados: CPU Modicon M340 (números de pieza BMXP34*)(V3.40 y anteriores), CPU Modicon M580 (números de pieza BMEP* y BMEH*)(V3.22 y anteriores), Modicon Quantum/Premium heredado (todas las versiones), Modicon Momentum MDI (171CBU*)(todas las versiones), Modicon MC80 (BMKC80)(V1.7 y anteriores) • https://www.se.com/us/en/download/document/SEVD-2022-221-02 • CWE-191: Integer Underflow (Wrap or Wraparound) •

CVSS: 9.1EPSS: 0%CPEs: 63EXPL: 0

Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller. Se presenta una vulnerabilidad de Omisión de Autenticación por Spoofing en EcoStruxure Control Expert (todas las versiones anteriores a V15.0 SP1, incluyendo todas las versiones de Unity Pro), EcoStruxure Control Expert versión V15.0 SP1, EcoStruxure Process Expert (todas las versiones, incluyendo todas las versiones de EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (todas las versiones), Modicon M580 CPU (todas las versiones - números de parte BMEP* y BMEH*), Modicon M340 CPU (todas las versiones - números de parte BMXP34*), que podría causar un acceso no autorizado en modo de lectura y escritura al controlador mediante el spoofing de la comunicación Modbus entre el software de ingeniería y el controlador • http://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-194-01 • CWE-290: Authentication Bypass by Spoofing •