9 results (0.002 seconds)

CVSS: 7.5EPSS: 0%CPEs: 10EXPL: 0

A vulnerability has been identified in EN100 Ethernet module DNP3 IP variant (All versions), EN100 Ethernet module IEC 104 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.40), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). Affected applications contains a memory corruption vulnerability while parsing specially crafted HTTP packets to /txtrace endpoint manupulating a specific argument. This could allow an attacker to crash the affected application leading to a denial of service condition Se ha identificado una vulnerabilidad en la variante DNP3 IP del módulo EN100 Ethernet (Todas las versiones), la variante IEC 104 del módulo EN100 Ethernet (Todas las versiones), la variante IEC 61850 del módulo EN100 Ethernet (Todas las versiones anteriores a la versión V4.40), la variante Modbus TCP del módulo EN100 Ethernet (Todas las versiones), la variante PROFINET IO del módulo EN100 Ethernet (Todas las versiones). Las aplicaciones afectadas contienen una vulnerabilidad de corrupción de memoria mientras analizan paquetes HTTP especialmente diseñados para el punto final /txtrace que manupulan un argumento específico. Esto podría permitir a un atacante bloquear la aplicación afectada, provocando una condición de denegación de servicio. • https://cert-portal.siemens.com/productcert/pdf/ssa-865333.pdf • CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer CWE-787: Out-of-bounds Write •

CVSS: 7.8EPSS: 0%CPEs: 6EXPL: 0

A vulnerability has been identified in EN100 Ethernet module DNP3 IP variant (All versions), EN100 Ethernet module IEC 104 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.37), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). Affected applications contains a memory corruption vulnerability while parsing specially crafted HTTP packets to /txtrace endpoint. This could allow an attacker to crash the affected application leading to a denial of service condition. Se ha identificado una vulnerabilidad en la variante DNP3 IP del módulo EN100 Ethernet (Todas las versiones), la variante IEC 104 del módulo EN100 Ethernet (Todas las versiones), la variante IEC 61850 del módulo EN100 Ethernet (Todas las versiones anteriores a V4.37), la variante Modbus TCP del módulo EN100 Ethernet (Todas las versiones), la variante PROFINET IO del módulo EN100 Ethernet (Todas las versiones). Las aplicaciones afectadas contienen una vulnerabilidad de corrupción de memoria mientras analizan paquetes HTTP especialmente diseñados para el endpoint /txtrace. • https://cert-portal.siemens.com/productcert/pdf/ssa-693555.pdf • CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer CWE-787: Out-of-bounds Write •

CVSS: 6.1EPSS: 0%CPEs: 6EXPL: 0

A vulnerability has been identified in EN100 Ethernet module DNP3 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.37), EN100 Ethernet module IEC104 variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). The web interface could allow Cross-Site Scripting (XSS) attacks if an attacker is able to modify content of particular web pages, causing the application to behave in unexpected ways for legitimate users. Successful exploitation does not require for an attacker to be authenticated to the web interface. This could allow the attacker to read or modify contents of the web application. At the time of advisory publication no public exploitation of this security. vulnerability was known. • https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdf https://www.us-cert.gov/ics/advisories/icsa-19-344-07 • CWE-79: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') •

CVSS: 5.3EPSS: 0%CPEs: 6EXPL: 0

A vulnerability has been identified in EN100 Ethernet module DNP3 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.37), EN100 Ethernet module IEC104 variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). A vulnerability in the integrated web server of the affected devices could allow unauthorized attackers to obtain sensitive information about the device, including logs and configurations. At the time of advisory publication no public exploitation of this security vulnerability was known. Se ha identificado una vulnerabilidad en la variante DNP3 del módulo EN100 Ethernet (todas las versiones), la variante IEC 61850 del módulo EN100 Ethernet (todas las versiones anteriores a V4.37), la variante IEC104 del módulo EN100 Ethernet (todas las versiones), la variante Modbus TCP del módulo EN100 Ethernet (todas las versiones), la variante PROFINET IO del módulo EN100 Ethernet (todas las versiones). Una vulnerabilidad en el servidor web integrado de los dispositivos afectados podría permitir a atacantes no autorizados obtener información confidencial sobre el dispositivo, incluyendo registros y configuraciones. • https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdf https://www.us-cert.gov/ics/advisories/icsa-19-344-07 • CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') CWE-23: Relative Path Traversal •

CVSS: 7.5EPSS: 0%CPEs: 6EXPL: 0

A vulnerability has been identified in EN100 Ethernet module DNP3 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.37), EN100 Ethernet module IEC104 variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). An unauthorized user could exploit a buffer overflow vulnerability in the webserver. Specially crafted packets sent could cause a Denial-of-Service condition and if certain conditions are met, the affected devices must be restarted manually to fully recover. At the time of advisory publication no public exploitation of this security vulnerability was known. Se ha identificado una vulnerabilidad en la variante DNP3 del módulo EN100 Ethernet (todas las versiones), la variante IEC 61850 del módulo EN100 Ethernet (todas las versiones anteriores a V4.37), la variante IEC104 del módulo EN100 Ethernet (todas las versiones), la variante Modbus TCP del módulo EN100 Ethernet (todas las versiones), la variante PROFINET IO del módulo EN100 Ethernet (todas las versiones). • https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdf https://www.us-cert.gov/ics/advisories/icsa-19-344-07 • CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer •