3 results (0.001 seconds)

CVSS: 6.1EPSS: 0%CPEs: 202EXPL: 0

26 Jun 2023 — Multiple WAGO devices in multiple versions may allow an authenticated remote attacker with high privileges to DoS the device by sending a specifically crafted packet to the CODESYS V2 runtime. • https://cert.vde.com/en/advisories/VDE-2023-006 • CWE-20: Improper Input Validation CWE-1288: Improper Validation of Consistency within Input •

CVSS: 6.1EPSS: 0%CPEs: 202EXPL: 0

26 Jun 2023 — Multiple WAGO devices in multiple versions may allow an authenticated remote attacker with high privileges to DoS the device by sending a malformed packet. • https://cert.vde.com/en/advisories/VDE-2023-006 • CWE-20: Improper Input Validation CWE-1288: Improper Validation of Consistency within Input •

CVSS: 9.8EPSS: 1%CPEs: 19EXPL: 0

13 Feb 2018 — An Improper Authentication issue was discovered in WAGO PFC200 Series 3S CoDeSys Runtime versions 2.3.X and 2.4.X. An attacker can execute different unauthenticated remote operations because of the CoDeSys Runtime application, which is available via network by default on Port 2455. An attacker could execute some unauthenticated commands such as reading, writing, or deleting arbitrary files, or manipulate the PLC application during runtime by sending specially-crafted TCP packets to Port 2455. Se ha descubie... • https://ics-cert.us-cert.gov/advisories/ICSA-18-044-01 • CWE-287: Improper Authentication •