Honeywell ControlEdge through R151.1 uses Hard-coded Credentials. According to FSCT-2022-0056, there is a Honeywell ControlEdge hardcoded credentials issue. The affected components are characterized as: SSH. The potential impact is: Remote code execution, manipulate configuration, denial of service. The Honeywell ControlEdge PLC and RTU product line exposes an SSH service on port 22/TCP. Login as root to this service is permitted and credentials for the root user are hardcoded without automatically changing them upon first commissioning. The credentials for the SSH service are hardcoded in the firmware. The credentials grant an attacker access to a root shell on the PLC/RTU, allowing for remote code execution, configuration manipulation and denial of service.
Honeywell ControlEdge versiones hasta R151.1, usa credenciales embebidas. De acuerdo con FSCT-2022-0056, se presenta un problema de credenciales embebidas de Honeywell ControlEdge. Los componentes afectados son caracterizados como: SSH. El impacto potencial es: Ejecución de código Remota, manipulación de la configuración, denegación de servicio. La línea de productos PLC y RTU de Honeywell ControlEdge expone un servicio SSH en el puerto 22/TCP. Es permitido el inicio de sesión como root en este servicio y las credenciales para el usuario root están embebidas sin cambiarlas automáticamente en la primera puesta en marcha. Las credenciales para el servicio SSH están embebidas en el firmware. Las credenciales conceden a un atacante acceso a un shell root en el PLC/RTU, lo que permite una ejecución de código remota, manipulación de la configuración y denegación de servicio
CVSS Scores
SSVC
- Decision:-
Timeline
- 2022-05-06 CVE Reserved
- 2022-08-31 CVE Published
- 2024-08-03 CVE Updated
- 2024-11-22 EPSS Updated
- ---------- Exploited in Wild
- ---------- KEV Due Date
- ---------- First Exploit
CWE
- CWE-798: Use of Hard-coded Credentials
CAPEC
References (2)
URL | Tag | Source |
---|---|---|
https://www.cisa.gov/uscert/ics/advisories/icsa-22-242-06 | Third Party Advisory | |
https://www.forescout.com/blog | Not Applicable |
URL | Date | SRC |
---|
URL | Date | SRC |
---|
URL | Date | SRC |
---|
Affected Vendors, Products, and Versions
Vendor | Product | Version | Other | Status | ||||||
---|---|---|---|---|---|---|---|---|---|---|
Vendor | Product | Version | Other | Status | <-- --> | Vendor | Product | Version | Other | Status |
Honeywell Search vendor "Honeywell" | Controledge Plc Firmware Search vendor "Honeywell" for product "Controledge Plc Firmware" | < r151.2 Search vendor "Honeywell" for product "Controledge Plc Firmware" and version " < r151.2" | - |
Affected
| in | Honeywell Search vendor "Honeywell" | Controledge Plc Search vendor "Honeywell" for product "Controledge Plc" | - | - |
Safe
|
Honeywell Search vendor "Honeywell" | Controledge Rtu Firmware Search vendor "Honeywell" for product "Controledge Rtu Firmware" | < r151.2 Search vendor "Honeywell" for product "Controledge Rtu Firmware" and version " < r151.2" | - |
Affected
| in | Honeywell Search vendor "Honeywell" | Controledge Rtu Search vendor "Honeywell" for product "Controledge Rtu" | - | - |
Safe
|