// For flags

CVE-2025-50121

Schneider Electric EcoStruxure IT Data Center Expert 8.3 Remote Code Execution

Severity Score

9.5
*CVSS v4

Exploit Likelihood

*EPSS

Affected Versions

*CPE

Public Exploits

1
*Multiple Sources

Exploited in Wild

-
*KEV

Decision

Attend
*SSVC
Descriptions

CWE-78: Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection')
vulnerability exists that could cause unauthenticated remote code execution when a malicious folder is created
over the web interface HTTP when enabled. HTTP is disabled by default.

A CWE-78: Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection')
vulnerability exists that could cause unauthenticated remote code execution when a malicious folder is created
over the web interface HTTP when enabled. HTTP is disabled by default.

A CWE-78: Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability exists that could cause unauthenticated remote code execution when a malicious folder is created over the web interface HTTP when enabled. HTTP is disabled by default.

Schneider Electric EcoStruxure IT Data Center Expert versions 8.3 and below lacks authorization controls and allows anyone to masquerade as a NetBotz camera. A path traversal vulnerability enables an attacker to create a malicious folder name capable of injecting arguments into specific shell commands during application boot. By leveraging a separate server-side request forgery (SSRF) vulnerability, an attacker can chain these two issues to obtain a root shell from a completely unauthenticated perspective.

*Credits: N/A
CVSS Scores
Attack Vector
Network
Attack Complexity
Low
Attack Requirements
Present
Privileges Required
None
User Interaction
None
System
Vulnerable | Subsequent
Confidentiality
High
High
Integrity
High
Low
Availability
High
High
Attack Vector
Network
Attack Complexity
Low
Privileges Required
None
User Interaction
None
Scope
Changed
Confidentiality
High
Integrity
High
Availability
High
Attack Vector
Network
Attack Complexity
Low
Authentication
None
Confidentiality
Complete
Integrity
Complete
Availability
Complete
* Common Vulnerability Scoring System
SSVC
  • Decision:Attend
Exploitation
None
Automatable
Yes
Tech. Impact
Total
* Organization's Worst-case Scenario
Timeline
  • 2025-06-12 CVE Reserved
  • 2025-07-10 CVE Published
  • 2025-07-10 First Exploit
  • 2025-07-13 CVE Updated
  • 2025-07-17 EPSS Updated
  • ---------- Exploited in Wild
  • ---------- KEV Due Date
CWE
  • CWE-78: Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection')
CAPEC
Affected Vendors, Products, and Versions
Vendor Product Version Other Status
Vendor Product Version Other Status <-- --> Vendor Product Version Other Status
Schneider-electric
Search vendor "Schneider-electric"
Data Center Expert
Search vendor "Schneider-electric" for product "Data Center Expert"
*-
Affected