4 results (0.009 seconds)

CVSS: 7.5EPSS: 0%CPEs: 9EXPL: 0

Vulnerability exists in SCI IEC 60870-5-104 and HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Specially crafted messages sent to the mentioned components are not validated properly and can result in buffer overflow and as final consequence to a reboot of an RTU500 CMU. Existe una vulnerabilidad en SCI IEC 60870-5-104 y HCI IEC 60870-5-104 que afecta a las versiones de productos de RTU500 series que se enumeran a continuación. Los mensajes especialmente manipulados enviados a los componentes mencionados no se validan correctamente y pueden provocar un desbordamiento de búfer y, como consecuencia final, un reinicio de una CMU RTU500. • https://publisher.hitachienergy.com/preview?DocumentId=8DBD000184&languageCode=en&Preview=true • CWE-20: Improper Input Validation CWE-120: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') •

CVSS: 7.5EPSS: 0%CPEs: 74EXPL: 0

A vulnerability exists in the IEC 61850 communication stack that affects multiple Hitachi Energy products.  An attacker could exploit the vulnerability by using a specially crafted message sequence, to force the IEC 61850 MMS-server communication stack, to stop accepting new MMS-client connections.  Already existing/established client-server connections are not affected. List of affected CPEs: * cpe:2.3:o:hitachienergy:fox61x_tego1:r15b08:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r2a16_3:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r2a16:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1e01:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1d02:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1c07:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:fox61x_tego1:r1b02:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:gms600:1.3.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.1.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.5.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.6.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.6.0.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.7.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.7.2:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:1.8.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:2.0.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:2.1.0.4:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:itt600_sa_explorer:2.1.0.5:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.*:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.4:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:microscada_x_sys600:10.4.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:mms:2.2.3:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:pwc600:1.0:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:pwc600:1.1:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:pwc600:1.2:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:reb500:7:*:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:reb500:8:*:*:*:*:*:*:* * cpe:2.3:o:hitachienergy:relion670:1.2. • https://search.abb.com/library/Download.aspx?DocumentID=8DBD000124&LanguageCode=en&DocumentPartId=&Action=Launch https://search.abb.com/library/Download.aspx?DocumentID=8DBD000125&LanguageCode=en&DocumentPartId=&Action=Launch https://search.abb.com/library/Download.aspx?DocumentID=8DBD000126&LanguageCode=en&DocumentPartId=&Action=Launch https://search.abb.com/library/Download.aspx?DocumentID=8DBD000127&LanguageCode=en&DocumentPartId=&Action=Launch https://search.abb.com/library/Download.aspx? • CWE-404: Improper Resource Shutdown or Release •

CVSS: 7.8EPSS: 0%CPEs: 7EXPL: 0

A vulnerability in the HCI Modbus TCP COMPONENT of Hitachi Energy RTU500 series CMU Firmware that is caused by the validation error in the length information carried in MBAP header allows an ATTACKER to reboot the device by sending a special crafted message. This issue affects: Hitachi Energy RTU500 series CMU Firmware 12.0.*; 12.2.*; 12.4.*; 12.6.*; 12.7.*; 13.2.*. Una vulnerabilidad en el COMPONENTE HCI Modbus TCP del firmware de la CMU de la serie RTU500 de Hitachi Energy, causada por un error de comprobación en la información de longitud que se transmite en el encabezado MBAP, permite a un ATACANTE reiniciar el dispositivo mediante el envío de un mensaje especialmente diseñado. Este problema afecta a: Hitachi Energy RTU500 series CMU Firmware versiones 12.0.*; 12.2.*; 12.4.*; 12.6.*; 12.7.*; 13.2.* A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. • https://search.abb.com/library/Download.aspx?DocumentID=8DBD000103&LanguageCode=en&DocumentPartId=&Action=Launch https://publisher.hitachienergy.com/preview?DocumentID=8DBD000103&LanguageCode=en&DocumentPartId=&Action=Launch • CWE-20: Improper Input Validation CWE-1284: Improper Validation of Specified Quantity in Input •

CVSS: 7.5EPSS: 0%CPEs: 4EXPL: 0

Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions). Una vulnerabilidad de comprobación de entrada inapropiada en el analizador de APDU en la función IEC 60870-5-104 de la interfaz de comunicación bidireccional (BCI) de la serie RTU500 de Hitachi Energy permite a un atacante causar el reinicio de la CMU RTU500 receptora en la que está habilitado el BCI cuando recibe un mensaje especialmente diseñado. Por defecto, la función BCI IEC 60870-5-104 está deshabilitada (no configurada). • https://search.abb.com/library/Download.aspx?DocumentID=8DBD000063&LanguageCode=en&DocumentPartId=&Action=Launch • CWE-20: Improper Input Validation •