CVSS: 8.6EPSS: 0%CPEs: 12EXPL: 0

A vulnerability exists in the Rockwell Automation controllers that allows a malformed CIP request to cause a major non-recoverable fault (MNRF) and a denial-of-service condition (DOS). Existe una vulnerabilidad en los controladores de Rockwell Automation que permite que una solicitud CIP con formato incorrecto cause una falla mayor no recuperable (MNRF) y una condición de Denegación de Servicio (DoS) (DOS). • https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1137757 • CWE-20: Improper Input Validation •

CVSS: 8.6EPSS: 0%CPEs: 18EXPL: 0

The connection establishment algorithm found in Rockwell Automation CompactLogix 5370 and ControlLogix 5570 versions 33 and prior does not sufficiently manage its control flow during execution, creating an infinite loop. This may allow an attacker to send specially crafted CIP packet requests to a controller, which may cause denial-of-service conditions in communications with other products. El algoritmo de establecimiento de conexión encontrado en Rockwell Automation CompactLogix 5370 and ControlLogix 5570 versiones 33 y anteriores, no administra suficientemente su flujo de control durante la ejecución, creando un bucle infinito. Esto puede permitir a un atacante enviar peticiones de paquetes CIP especialmente diseñados a un controlador, lo que puede causar condiciones de denegación de servicio en las comunicaciones con otros productos • https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1130398 https://www.cisa.gov/uscert/ics/advisories/icsa-21-061-02 • CWE-20: Improper Input Validation •

CVSS: 8.6EPSS: 0%CPEs: 18EXPL: 0

A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online. Un mensaje de protocolo industrial común de clase 3 malformado con una conexión en caché puede causar una condición de denegación de servicio en los controladores Logix de Rockwell Automation, lo que resulta en una falla importante no recuperable. Si el dispositivo de destino deja de estar disponible, un usuario tendría que borrar el fallo y volver a descargar el archivo de proyecto del usuario para que el dispositivo vuelva a estar en línea • https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1135559 https://www.cisa.gov/uscert/ics/advisories/icsa-22-144-01 • CWE-400: Uncontrolled Resource Consumption •