CVE-2024-6207
https://notcve.org/view.php?id=CVE-2024-6207
14 Oct 2024 — CVE 2021-22681 https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1550.html and send a specially crafted CIP message to the device. If exploited, a threat actor could help prevent access to the legitimate user and end connections to connected devices including the workstation. To recover the controllers, a download is required which ends any process that the controller is running. • https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1707.html • CWE-20: Improper Input Validation •

CVE-2024-6077 – Rockwell Automation ControlLogix/GuardLogix 5580 and CompactLogix/Compact GuardLogix® 5380 Vulnerable to DoS vulnerability via CIP
https://notcve.org/view.php?id=CVE-2024-6077
12 Sep 2024 — A denial-of-service vulnerability exists in the Rockwell Automation affected products when specially crafted packets are sent to the CIP Security Object. If exploited the device will become unavailable and require a factory reset to recover. • https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1963.html • CWE-20: Improper Input Validation •

CVE-2024-21916 – Rockwell Automation Denial-of-service Vulnerability in ICE1 Controller
https://notcve.org/view.php?id=CVE-2024-21916
31 Jan 2024 — A denial-of-service vulnerability exists in specific Rockwell Automation ControlLogix ang GuardLogix controllers. If exploited, the product could potentially experience a major nonrecoverable fault (MNRF). The device will restart itself to recover from the MNRF. Existe una vulnerabilidad de denegación de servicio en controladores Rockwell Automation ControlLogix ang GuardLogix. Si se explota, el producto podría experimentar un fallo importante no recuperable (MNRF). • https://www.rockwellautomation.com/en-us/support/advisory.SD1661.html • CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer •

CVE-2022-3157 – Rockwell Automation GuardLogix and ControlLogix controllers Vulnerable to Denial-Of-Service Attack
https://notcve.org/view.php?id=CVE-2022-3157
16 Dec 2022 — A vulnerability exists in the Rockwell Automation controllers that allows a malformed CIP request to cause a major non-recoverable fault (MNRF) and a denial-of-service condition (DOS). Existe una vulnerabilidad en los controladores de Rockwell Automation que permite que una solicitud CIP con formato incorrecto cause una falla mayor no recuperable (MNRF) y una condición de Denegación de Servicio (DoS) (DOS). • https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1137757 • CWE-20: Improper Input Validation •

CVE-2020-6998 – Rockwell Automation CompactLogix 5370 and ControlLogix 5570 Controllers Improper Input Validation
https://notcve.org/view.php?id=CVE-2020-6998
27 Jul 2022 — The connection establishment algorithm found in Rockwell Automation CompactLogix 5370 and ControlLogix 5570 versions 33 and prior does not sufficiently manage its control flow during execution, creating an infinite loop. This may allow an attacker to send specially crafted CIP packet requests to a controller, which may cause denial-of-service conditions in communications with other products. El algoritmo de establecimiento de conexión encontrado en Rockwell Automation CompactLogix 5370 and ControlLogix 5570... • https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1130398 • CWE-20: Improper Input Validation •

CVE-2022-1797 – Rockwell Automation Logix Controllers Uncontrolled Resource Consumption
https://notcve.org/view.php?id=CVE-2022-1797
31 May 2022 — A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online. Un mensaje de protocolo industrial común de clase 3 malformado con una conexión en caché puede causar una condición de denegación de servicio en los controlad... • https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1135559 • CWE-400: Uncontrolled Resource Consumption •

CVE-2022-1161 – ICSA-22-090-05 Rockwell Automation Logix Controllers
https://notcve.org/view.php?id=CVE-2022-1161
11 Apr 2022 — An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other. Un atacante con la capacidad de modificar un programa de usuario puede cambiar el código del programa de usuario en algunos sistemas ControlLogix, CompactLogix y GuardLogix Control. Studio 5... • https://www.cisa.gov/uscert/ics/advisories/icsa-22-090-05 • CWE-829: Inclusion of Functionality from Untrusted Control Sphere •

CVE-2022-1159 – Rockwell Automation Studio 5000 Logix Designer Code Injection
https://notcve.org/view.php?id=CVE-2022-1159
01 Apr 2022 — Rockwell Automation Studio 5000 Logix Designer (all versions) are vulnerable when an attacker who achieves administrator access on a workstation running Studio 5000 Logix Designer could inject controller code undetectable to a user. Rockwell Automation Studio 5000 Logix Designer (todas las versiones) son vulnerables cuando un atacante que logra acceso de administrador en una estación de trabajo que ejecuta Studio 5000 Logix Designer podría inyectar código de controlador no detectable para un usuario • https://www.cisa.gov/uscert/ics/advisories/icsa-22-090-07 • CWE-94: Improper Control of Generation of Code ('Code Injection') •

CVE-2017-6024
https://notcve.org/view.php?id=CVE-2017-6024
06 May 2017 — A Resource Exhaustion issue was discovered in Rockwell Automation ControlLogix 5580 controllers V28.011, V28.012, and V28.013; ControlLogix 5580 controllers V29.011; CompactLogix 5380 controllers V28.011; and CompactLogix 5380 controllers V29.011. This vulnerability may allow an attacker to cause a denial of service condition by sending a series of specific CIP-based commands to the controller. Se ha descubierto un problema de agotamiento de recursos en Rockwell Automation ControlLogix 5580 en los controlad... • http://www.securityfocus.com/bid/98309 • CWE-400: Uncontrolled Resource Consumption •

CVE-2016-9343
https://notcve.org/view.php?id=CVE-2016-9343
13 Feb 2017 — An issue was discovered in Rockwell Automation Logix5000 Programmable Automation Controller FRN 16.00 through 21.00 (excluding all firmware versions prior to FRN 16.00, which are not affected). By sending malformed common industrial protocol (CIP) packet, an attacker may be able to overflow a stack-based buffer and execute code on the controller or initiate a nonrecoverable fault resulting in a denial of service. Ha sido descubierto un problema en Rockwell Automation Logix5000 Programmable Automation Contro... • http://www.securityfocus.com/bid/95304 • CWE-787: Out-of-bounds Write •