3 results (0.009 seconds)

CVSS: 9.8EPSS: 0%CPEs: 20EXPL: 0

Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer versiones 21 y posteriores, y RSLogix 5000 versiones 16 hasta 20, usan una clave para verificar que los controladores Logix se estén comunicando con Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer versiones 21 y posteriores y RSLogix 5000: Versiones 16 hasta 20, son vulnerables porque un atacante no autenticado podría pasar por alto este mecanismo de comprobación y autenticarse con Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550 , 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800 • https://us-cert.cisa.gov/ics/advisories/icsa-21-056-03 • CWE-522: Insufficiently Protected Credentials •

CVSS: 5.0EPSS: 0%CPEs: 6EXPL: 0

The FactoryTalk (FT) RNADiagReceiver service in Rockwell Automation Allen-Bradley FactoryTalk CPR9 through SR5 and RSLogix 5000 17 through 20 allows remote attackers to cause a denial of service (out-of-bounds read) via a crafted packet. El servicio FactoryTalk (FT) RNADiagReceiver en Rockwell Automation Allen-Bradley FactoryTalk CPR9 hasta SR5 y RSLogix 5000 17 hasta 20 permite a atacantes remotos provocar una denegación de servicio (lectura fuera del límite) a través de un paquete manipulado. • http://rockwellautomation.custhelp.com/app/answers/detail/a_id/469937 http://www.us-cert.gov/control_systems/pdf/ICSA-12-088-01.pdf • CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer •

CVSS: 5.0EPSS: 76%CPEs: 6EXPL: 1

The FactoryTalk (FT) RNADiagReceiver service in Rockwell Automation Allen-Bradley FactoryTalk CPR9 through SR5 and RSLogix 5000 17 through 20 does not properly handle the return value from an unspecified function, which allows remote attackers to cause a denial of service (service outage) via a crafted packet. El servicio FactoryTalk (FT) RNADiagReceiver en Rockwell Automation Allen-Bradley FactoryTalk CPR9 hasta SR5 y RSLogix 5000 17 hasta 20 no gestiona de forma adecuada el valor de retorno de una función específica, lo que permite a atacantes remotos provocar una denegación de servicio (corte de servicio) a través de un paquete manipulado. • https://www.exploit-db.com/exploits/36570 http://rockwellautomation.custhelp.com/app/answers/detail/a_id/469937 http://www.us-cert.gov/control_systems/pdf/ICSA-12-088-01.pdf • CWE-20: Improper Input Validation •