5 results (0.013 seconds)

CVSS: 5.1EPSS: 0%CPEs: 2EXPL: 0

A CWE-20: Improper Input Validation vulnerability exists that could cause the device watchdog function to be disabled if the attacker had access to privileged user credentials. Affected Products: Easergy P5 (V01.401.102 and prior) Una CWE-20: Se presenta una vulnerabilidad de Comprobación de Entrada Inapropiada que podría causar que de la función de vigilancia sea deshabilitada del dispositivo si el atacante tuviera acceso a credenciales de usuario privilegiadas. Productos afectados: Easergy P5 (versiones V01.401.102 y anteriores) • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-193-04&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2022-193-04_Easergy_P5_Security_Notification.pdf • CWE-20: Improper Input Validation •

CVSS: 6.7EPSS: 0%CPEs: 2EXPL: 0

A CWE-327: Use of a Broken or Risky Cryptographic Algorithm vulnerability exists where weak cipher suites can be used for the SSH connection between Easergy Pro software and the device, which may allow an attacker to observe protected communication details. Affected Products: Easergy P5 (V01.401.102 and prior) Una CWE-327: Se presenta una vulnerabilidad de Uso de un Algoritmo Criptográfico Roto o Arriesgado en la que pueden usarse suites de cifrado débiles para la conexión SSH entre el software Easergy Pro y el dispositivo, lo que puede permitir a un atacante observar los detalles de la comunicación protegida. Productos afectados: Easergy P5 (versiones V01.401.102 y anteriores) • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-193-04&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2022-193-04_Easergy_P5_Security_Notification.pdf • CWE-327: Use of a Broken or Risky Cryptographic Algorithm •

CVSS: 9.8EPSS: 0%CPEs: 2EXPL: 0

A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could result in remote code execution or the crash of HTTPs stack which is used for the device Web HMI. Affected Products: Easergy P5 (V01.401.102 and prior) Una CWE-120: Se presenta una vulnerabilidad de Copia del Búfer sin Comprobar el Tamaño de la Entrada que podría resultar en una ejecución de código remota o en el bloqueo de la pila HTTPs que es usada para la HMI web del dispositivo. Productos afectados: Easergy P5 (versiones V01.401.102 y anteriores) • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-193-04&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2022-193-04_Easergy_P5_Security_Notification.pdf • CWE-120: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') •

CVSS: 8.8EPSS: 0%CPEs: 2EXPL: 0

A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could lead to a buffer overflow causing program crashes and arbitrary code execution when specially crafted packets are sent to the device over the network. Protection functions and tripping function via GOOSE can be impacted. Affected Product: Easergy P5 (All firmware versions prior to V01.401.101) Una CWE-120: Se presenta una vulnerabilidad de Copia del Búfer sin Comprobar el Tamaño de la Entrada que podría conllevar a un desbordamiento del búfer causando un bloqueo del programa y una ejecución de código arbitrario cuando son enviados paquetes especialmente diseñados al dispositivo a través de la red. Las funciones Protection y la función tripping por medio de GOOSE pueden verse afectadas. Producto afectado: Easergy P5 (todas las versiones de firmware anteriores a V01.401.101) • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-011-03 • CWE-120: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') •

CVSS: 7.5EPSS: 0%CPEs: 2EXPL: 0

A CWE-798: Use of Hard-coded Credentials vulnerability exists that could result in information disclosure. If an attacker were to obtain the SSH cryptographic key for the device and take active control of the local operational network connected to the product they could potentially observe and manipulate traffic associated with product configuration. Affected Product: Easergy P5 (All firmware versions prior to V01.401.101) Una CWE-798: Se presenta un uso de credenciales embebidas que podría resultar en una divulgación de información. Si un atacante obtuviera la clave criptográfica SSH del dispositivo y tomara el control activo de la red operativa local conectada al producto, podría observar y manipular el tráfico asociado a la configuración del producto. Producto afectado: Easergy P5 (todas las versiones de firmware anteriores a V01.401.101) • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-011-03 • CWE-798: Use of Hard-coded Credentials •