4 results (0.006 seconds)

CVSS: 7.8EPSS: 0%CPEs: 4EXPL: 0

Improper Input Validation vulnerability exists in Modicon M241/M251 logic controllers firmware prior to V5.1.9.1 that could cause denial of service when specific crafted requests are sent to the controller over HTTP. Se presenta una vulnerabilidad de Comprobación Inapropiada de Entrada en los controladores lógicos Modicon M241/M251 versiones del firmware anteriores a V5.1.9.1, que podría causar una denegación de servicio cuando peticiones específicas diseñadas son enviadas al controlador a través de HTTP • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-130-05 • CWE-20: Improper Input Validation •

CVSS: 9.1EPSS: 2%CPEs: 4EXPL: 1

A Use of Insufficiently Random Values issue was discovered in Schneider Electric Modicon PLCs Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The session numbers generated by the web application are lacking randomization and are shared between several users. This may allow a current session to be compromised. Un problema de uso de valores aleatorios insuficientes fue encontrado en Schneider Electric Modicon PLCs Modicon M241, versiones de firmware anteriores a 4.0.5.11, y Modicon M251, versiones de firmware anteriores a 4.0.5.11. Los números de sesión generados por la aplicación web carecen de aleatorización y son compartidos entre varios usuarios. • https://www.exploit-db.com/exploits/45918 http://www.securityfocus.com/bid/97254 https://ics-cert.us-cert.gov/advisories/ICSA-17-089-02 • CWE-330: Use of Insufficiently Random Values •

CVSS: 9.8EPSS: 0%CPEs: 4EXPL: 0

An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing. Sniffed credentials could then be used to log into the web application. Un problema de credenciales protegidas insuficientemente fue detectado en PLCs Modicon M241, y Modicon M251 de Schneider Electric, en todas las versiones de firmware. Las credenciales de inicio de sesión se envían por medio de la red con codificación Base64 dejándolas susceptibles a ser espiadas. • http://www.securityfocus.com/bid/97254 https://ics-cert.us-cert.gov/advisories/ICSA-17-089-02 • CWE-522: Insufficiently Protected Credentials •

CVSS: 6.5EPSS: 0%CPEs: 6EXPL: 0

A Predictable Value Range from Previous Values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections. Un problema de Rango de Valor Predecible de Valores Anteriores fue detectado en PLCs Modicon M221, versiones de firmware anteriores a 1.5.0.0, Modicon M241, versiones de firmware anteriores a la 4.0.5.11, y Modicon M251, versiones de firmware anteriores a la 4.0.5.11 de Schneider Electric. Los productos afectados generan números de secuencia inicial TCP de aleatoriedad insuficientemente que pueden permitir a un atacante predecir los números de los valores anteriores. • http://www.securityfocus.com/bid/97254 https://ics-cert.us-cert.gov/advisories/ICSA-17-089-02 • CWE-331: Insufficient Entropy CWE-343: Predictable Value Range from Previous Values •