8 results (0.009 seconds)

CVSS: 6.8EPSS: 0%CPEs: 41EXPL: 0

CWE-119: Buffer errors vulnerability exists in Modicon M580 with firmware prior to V2.50, Modicon M340 with firmware prior to V3.01, BMxCRA312xx with firmware prior to V2.40, All firmware versions of Modicon Premium and 140CRA312xxx when sending a specially crafted Modbus packet, which could cause a denial of service to the device that would force a restart to restore availability. CWE-119: Existe una vulnerabilidad de errores de búfer en Modicon M580 con firmware anterior a V2.50, Modicon M340 con firmware anterior a V3.01, BMxCRA312xx con firmware anterior a V2.40 y todas las versiones de firmware de Modicon Premium y 140CRA312xxx al enviar un paquete Modbus especialmente creado, que podría generar una Denegación de Servicio al dispositivo que forzaría un reinicio para restaurar la disponibilidad. • https://www.schneider-electric.com/en/download/document/SEVD-2019-134-10 • CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer •

CVSS: 7.5EPSS: 0%CPEs: 38EXPL: 0

A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists which could cause a possible Denial of Service when specific Modbus frames are sent to the controller in the products: Modicon M340 - firmware versions prior to V3.01, Modicon M580 - firmware versions prior to V2.80, All firmware versions of Modicon Quantum and Modicon Premium. Una CWE-754: Existe una vulnerabilidad de Comprobación Inapropiada para condiciones inusuales o excepcionales, que podría generar una posible Denegación de Servicio cuando se envían tramas Modbus específicas hacia el controlador en los productos: Modicon M340 - versiones de firmware anteriores a la V3.01, Modicon M580 - versiones de firmware anteriores a V2.80, y todas las versiones de firmware de Modicon Quantum y Modicon Premium. • http://www.securityfocus.com/bid/109004 https://www.schneider-electric.com/en/download/document/SEVD-2019-134-05 • CWE-754: Improper Check for Unusual or Exceptional Conditions •

CVSS: 10.0EPSS: 0%CPEs: 120EXPL: 0

Hard coded accounts exist in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. Existen cuentas embebidas en los controladores Modicon Premium, Modicon Quantum, Modicon M340 y BMXNOR0200, de Schneider Electric, en todas las versiones de los módulos de comunicación. • http://www.securityfocus.com/bid/103542 https://ics-cert.us-cert.gov/advisories/ICSA-18-086-01 https://www.schneider-electric.com/en/download/document/SEVD-2018-081-01 • CWE-798: Use of Hard-coded Credentials •

CVSS: 7.5EPSS: 0%CPEs: 120EXPL: 0

A vulnerability exists in the web services to process SOAP requests in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow result in a buffer overflow. Existe una vulnerabilidad en los servicios web que procesan peticiones SOAP en Modicon M340, Modicon Premium, Modicon Quantum PLC y BMXNOR0200, de Schneider Electric, que podría conducir a un desbordamiento de búfer. • https://www.schneider-electric.com/en/download/document/SEVD-2018-081-02 • CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer •

CVSS: 9.8EPSS: 0%CPEs: 120EXPL: 0

Vulnerable hash algorithms exists in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. The algorithm used to encrypt the password is vulnerable to hash collision attacks. Existen algoritmos de hash vulnerables en los controladores Modicon Premium, Modicon Quantum, Modicon M340 y BMXNOR0200, de Schneider Electric, en todas las versiones de los módulos de comunicación. El algoritmo empleado para cifrar la contraseña es vulnerable a ataques de colisión de hash. • http://www.securityfocus.com/bid/103543 https://ics-cert.us-cert.gov/advisories/ICSA-18-086-01 https://www.schneider-electric.com/en/download/document/SEVD-2018-081-01 • CWE-326: Inadequate Encryption Strength •