7 results (0.009 seconds)

CVSS: 5.9EPSS: 0%CPEs: 36EXPL: 0

A vulnerability has been identified in SIMATIC CP 1626 (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V20.8), SIMATIC HMI Panel (incl. SIPLUS variants) (All versions), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.4.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.8.1), SIMATIC S7-1500 Software Controller (All versions < V20.8), SIMATIC S7-PLCSIM Advanced (All versions < V3.0), SIMATIC STEP 7 (TIA Portal) (All versions < V16), SIMATIC WinCC (TIA Portal) (All versions < V16), SIMATIC WinCC OA (All versions < V3.16 P013), SIMATIC WinCC Runtime Advanced (All versions < V16), SIMATIC WinCC Runtime Professional (All versions < V16), TIM 1531 IRC (incl. • https://cert-portal.siemens.com/productcert/pdf/ssa-232418.pdf https://cert-portal.siemens.com/productcert/pdf/ssa-273799.pdf https://www.us-cert.gov/ics/advisories/icsa-19-344-04 • CWE-327: Use of a Broken or Risky Cryptographic Algorithm •

CVSS: 10.0EPSS: 26%CPEs: 5EXPL: 1

An exploitable heap overflow vulnerability exists in the WkbProgramLow function of WibuKey Network server management, version 6.40.2402.500. A specially crafted TCP packet can cause a heap overflow, potentially leading to remote code execution. An attacker can send a malformed TCP packet to trigger this vulnerability. Existe una vulnerabilidad de desbordamiento de memoria dinámica (heap) explotable en la función WkbProgramLow de WibuKey Network server management en su versión 6.40.2402.500. Un paquete TCP especialmente manipulado puede provocar un desbordamiento de memoria dinámica (heap), lo que podría dar lugar a la ejecución remota de código. • http://www.securityfocus.com/bid/107005 https://cert-portal.siemens.com/productcert/pdf/ssa-760124.pdf https://cert-portal.siemens.com/productcert/pdf/ssa-844562.pdf https://cert-portal.siemens.com/productcert/pdf/ssa-902727.pdf https://talosintelligence.com/vulnerability_reports/TALOS-2018-0659 • CWE-787: Out-of-bounds Write •

CVSS: 9.1EPSS: 0%CPEs: 1EXPL: 0

A vulnerability has been identified in SIMATIC WinCC OA V3.14 and prior (All versions < V3.14-P021). Improper access control to a data point of the affected product could allow an unauthenticated remote user to escalate its privileges in the context of SIMATIC WinCC OA V3.14. This vulnerability could be exploited by an attacker with network access to port 5678/TCP of the SIMATIC WinCC OA V3.14 server. Successful exploitation requires no user privileges and no user interaction. This vulnerability could allow an attacker to compromise integrity and availability of the SIMATIC WinCC OA system. • http://www.securityfocus.com/bid/105332 https://cert-portal.siemens.com/productcert/pdf/ssa-346256.pdf • CWE-269: Improper Privilege Management •

CVSS: 5.0EPSS: 0%CPEs: 1EXPL: 0

Siemens SIMATIC WinCC OA before 3.12 P002 January uses a weak hash algorithm for passwords, which makes it easier for remote attackers to obtain access via a brute-force attack. Siemens SIMATIC WinCC OA anterior a 3.12 P002 January usa un algoritmo hash débil para las contraseñas, lo que hace más fácil para atacantes remotos obtener acceso a través de un ataque de fuerza bruta. • http://ics-cert.us-cert.gov/advisories/ICSA-14-035-01 http://osvdb.org/102809 http://www.siemens.com/innovation/pool/de/forschungsfelder/siemens_security_advisory_ssa-342587.pdf https://exchange.xforce.ibmcloud.com/vulnerabilities/90934 • CWE-310: Cryptographic Issues •

CVSS: 5.0EPSS: 2%CPEs: 1EXPL: 0

Siemens SIMATIC WinCC OA before 3.12 P002 January allows remote attackers to cause a denial of service (monitoring-service outage) via malformed HTTP requests to port 4999. Siemens SIMATIC WinCC OA anterior a 3.12 P002 January permite a atacantes remotos causar una denegación de servicio (interrupción del servicio de monitorización) a través de peticiones HTTP malformadas hacia el puerto TCP 4999. • http://ics-cert.us-cert.gov/advisories/ICSA-14-035-01 http://osvdb.org/102812 http://secunia.com/advisories/56651 http://www.securityfocus.com/bid/65347 http://www.siemens.com/innovation/pool/de/forschungsfelder/siemens_security_advisory_ssa-342587.pdf https://exchange.xforce.ibmcloud.com/vulnerabilities/90936 • CWE-399: Resource Management Errors •