CVE-2018-10589 – Advantech WebAccess webvrpcs Command Injection Remote Code Execution Vulnerability
https://notcve.org/view.php?id=CVE-2018-10589
In Advantech WebAccess versions V8.2_20170817 and prior, WebAccess versions V8.3.0 and prior, WebAccess Dashboard versions V.2.0.15 and prior, WebAccess Scada Node versions prior to 8.3.1, and WebAccess/NMS 2.0.3 and prior, a path transversal vulnerability has been identified, which may allow an attacker to execute arbitrary code. En Advantech WebAccess en versiones V8.2_20170817 y anteriores, WebAccess en versiones V8.3.0 y anteriores, WebAccess Dashboard en versiones V.2.0.15 y anteriores, WebAccess Scada Node en versiones anteriores a la 8.3.1 y WebAccess/NMS 2.0.3 y anteriores, se ha identificado una vulnerabilidad de salto de directorio que podría permitir que un atacante ejecute código arbitrario. This vulnerability allows remote attackers to execute arbitrary code on vulnerable installations of Advantech WebAccess. Authentication is not required to exploit this vulnerability. The specific flaw exists within the implementation of the 0x2711 IOCTL in the webvrpcs process. The issue results from the lack of proper validation of a user-supplied path prior to using it in file operations. • http://www.securityfocus.com/bid/104190 https://ics-cert.us-cert.gov/advisories/ICSA-18-135-01 • CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') •
CVE-2018-7503 – Advantech WebAccess NMS DownloadAction Servlet Directory Traversal Information Disclosure Vulnerability
https://notcve.org/view.php?id=CVE-2018-7503
In Advantech WebAccess versions V8.2_20170817 and prior, WebAccess versions V8.3.0 and prior, WebAccess Dashboard versions V.2.0.15 and prior, WebAccess Scada Node versions prior to 8.3.1, and WebAccess/NMS 2.0.3 and prior, a path transversal vulnerability has been identified, which may allow an attacker to disclose sensitive information on the target. En Advantech WebAccess en versiones V8.2_20170817 y anteriores, WebAccess en versiones V8.3.0 y anteriores, WebAccess Dashboard en versiones V.2.0.15 y anteriores, WebAccess Scada Node en versiones anteriores a la 8.3.1 y WebAccess/NMS 2.0.3 y anteriores, se ha identificado una vulnerabilidad de salto de directorio que podría permitir que un atacante eevele información sensible en el objetivo. This vulnerability allows remote attackers to disclose sensitive information on vulnerable installations of Advantech WebAccess NMS. Authentication is not required to exploit this vulnerability. The specific flaw exists within the DownloadAction servlet. When parsing the filename and taskname parameters, the process does not properly validate a user-supplied path prior to using it in file operations. • http://www.securityfocus.com/bid/104190 https://ics-cert.us-cert.gov/advisories/ICSA-18-135-01 • CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') •
CVE-2018-7499 – Advantech WebAccess Node BwPSLinkZip Stack-based Buffer Overflow Remote Code Execution Vulnerability
https://notcve.org/view.php?id=CVE-2018-7499
In Advantech WebAccess versions V8.2_20170817 and prior, WebAccess versions V8.3.0 and prior, WebAccess Dashboard versions V.2.0.15 and prior, WebAccess Scada Node versions prior to 8.3.1, and WebAccess/NMS 2.0.3 and prior, several stack-based buffer overflow vulnerabilities have been identified, which may allow an attacker to execute arbitrary code. En Advantech WebAccess en versiones V8.2_20170817 y anteriores, WebAccess en versiones V8.3.0 y anteriores, WebAccess Dashboard en versiones V.2.0.15 y anteriores, WebAccess Scada Node en versiones anteriores a la 8.3.1 y WebAccess/NMS 2.0.3 y anteriores, se han identificado varias vulnerabilidades de desbordamiento de búfer que podrían permitir que un atacante ejecute código arbitrario. This vulnerability allows remote attackers to execute arbitrary code on affected installations of Advantech WebAccess Node. Authentication is not required to exploit this vulnerability. The specific flaw exists within BwPSLinkZip.exe, which is accessed through the 0x2711 IOCTL in the webvrpcs process. The issue results from the lack of proper validation of the length of user-supplied data prior to copying it to a fixed-length stack-based buffer. • http://www.securityfocus.com/bid/104190 https://ics-cert.us-cert.gov/advisories/ICSA-18-135-01 • CWE-121: Stack-based Buffer Overflow CWE-787: Out-of-bounds Write •
CVE-2018-10590
https://notcve.org/view.php?id=CVE-2018-10590
In Advantech WebAccess versions V8.2_20170817 and prior, WebAccess versions V8.3.0 and prior, WebAccess Dashboard versions V.2.0.15 and prior, WebAccess Scada Node versions prior to 8.3.1, and WebAccess/NMS 2.0.3 and prior, an information exposure vulnerability through directory listing has been identified, which may allow an attacker to find important files that are not normally visible. En Advantech WebAccess en versiones V8.2_20170817 y anteriores, WebAccess en versiones V8.3.0 y anteriores, WebAccess Dashboard en versiones V.2.0.15 y anteriores, WebAccess Scada Node en versiones anteriores a la 8.3.1 y WebAccess/NMS 2.0.3 y anteriores, se ha identificado una vulnerabilidad de exposición de información mediante el listado de directorios que podría permitir que un atacante encuentre archivos importantes que normalmente no suelen estar visibles. • http://www.securityfocus.com/bid/104190 https://ics-cert.us-cert.gov/advisories/ICSA-18-135-01 • CWE-538: Insertion of Sensitive Information into Externally-Accessible File or Directory CWE-548: Exposure of Information Through Directory Listing •
CVE-2018-7497 – Advantech WebAccess Node webvrpcs drawsrv Untrusted Pointer Dereference Remote Code Execution Vulnerability
https://notcve.org/view.php?id=CVE-2018-7497
In Advantech WebAccess versions V8.2_20170817 and prior, WebAccess versions V8.3.0 and prior, WebAccess Dashboard versions V.2.0.15 and prior, WebAccess Scada Node versions prior to 8.3.1, and WebAccess/NMS 2.0.3 and prior, several untrusted pointer dereference vulnerabilities have been identified, which may allow an attacker to execute arbitrary code. En Advantech WebAccess en versiones V8.2_20170817 y anteriores, WebAccess en versiones V8.3.0 y anteriores, WebAccess Dashboard en versiones V.2.0.15 y anteriores, WebAccess Scada Node en versiones anteriores a la 8.3.1 y WebAccess/NMS 2.0.3 y anteriores, se han identificado varias vulnerabilidades de desreferencia de puntero no fiable que podrían permitir que un atacante ejecute código arbitrario. This vulnerability allows remote attackers to execute arbitrary code on affected installations of Advantech WebAccess Node. Authentication is not required to exploit this vulnerability. The specific flaw exists within the implementation of the 0x2776 IOCTL in the webvrpcs process. The issue results from the lack of proper validation of a user-supplied value prior to dereferencing it as a pointer. • http://www.securityfocus.com/bid/104190 https://ics-cert.us-cert.gov/advisories/ICSA-18-135-01 • CWE-476: NULL Pointer Dereference CWE-822: Untrusted Pointer Dereference •