Page 2 of 35 results (0.002 seconds)

CVSS: 7.5EPSS: 1%CPEs: 6EXPL: 0

Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic function utilized to protect the password in MicroLogix is discoverable. Rockwell Automation MicroLogix 1400 Controllers Series B versiones v21.001 y anteriores, Series A, todas las versiones, MicroLogix 1100 Controller, todas las versiones, RSLogix 500 Software versiones v12.001 y anteriores. La función criptográfica usada para proteger la contraseña en MicroLogix es detectable. • https://www.us-cert.gov/ics/advisories/icsa-20-070-06 • CWE-327: Use of a Broken or Risky Cryptographic Algorithm •

CVSS: 10.0EPSS: 2%CPEs: 6EXPL: 0

Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, The cryptographic key utilized to help protect the account password is hard coded into the RSLogix 500 binary file. An attacker could identify cryptographic keys and use it for further cryptographic attacks that could ultimately lead to a remote attacker gaining unauthorized access to the controller. Rockwell Automation MicroLogix 1400 Controllers Series B versiones v21.001 y anteriores, Series A, todas las versiones, MicroLogix 1100 Controller, todas las versiones, RSLogix 500 Software versiones v12.001 y anteriores; La clave criptográfica usada para ayudar a proteger la contraseña de cuenta está embebida en el archivo binario de RSLogix 500. Un atacante podría identificar claves criptográficas y usarlas para nuevos ataques criptográficos que finalmente podrían conllevar a que un atacante remoto consiga acceso no autorizado al controlador. • https://www.us-cert.gov/ics/advisories/icsa-20-070-06 • CWE-321: Use of Hard-coded Cryptographic Key CWE-798: Use of Hard-coded Credentials •

CVSS: 7.5EPSS: 0%CPEs: 6EXPL: 0

Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, A remote, unauthenticated attacker can send a request from the RSLogix 500 software to the victim’s MicroLogix controller. The controller will then respond to the client with used password values to authenticate the user on the client-side. This method of authentication may allow an attacker to bypass authentication altogether, disclose sensitive information, or leak credentials. Rockwell Automation MicroLogix 1400 Controllers Series B versiones v21.001 y anteriores, Series A, todas las versiones, MicroLogix 1100 Controller, todas las versiones, RSLogix 500 Software versiones v12.001 y anteriores, un atacante no autenticado remoto puede enviar una petición desde el software RSLogix 500 hacia el controlador MicroLogix de la víctima. El controlador responderá al cliente con los valores de contraseña usados para autenticar al usuario en el lado del cliente. • https://www.us-cert.gov/ics/advisories/icsa-20-070-06 • CWE-287: Improper Authentication CWE-603: Use of Client-Side Authentication •

CVSS: 3.3EPSS: 0%CPEs: 6EXPL: 0

Rockwell Automation MicroLogix 1400 Controllers Series B v21.001 and prior, Series A, all versions, MicroLogix 1100 Controller, all versions, RSLogix 500 Software v12.001 and prior, If Simple Mail Transfer Protocol (SMTP) account data is saved in RSLogix 500, a local attacker with access to a victim’s project may be able to gather SMTP server authentication data as it is written to the project file in cleartext. Rockwell Automation MicroLogix 1400 Controllers Series B versiones v21.001 y anteriores, Series A, todas las versiones, MicroLogix 1100 Controller, todas las versiones, RSLogix 500 Software versiones v12.001 y anteriores, si los datos de la cuenta Simple Mail Transfer Protocol (SMTP) se guardan en RSLogix 500, un atacante local con acceso al proyecto de una víctima puede recopilar datos de autenticación del servidor SMTP tal y como están escritos en el archivo del proyecto en texto sin cifrar. • https://www.us-cert.gov/ics/advisories/icsa-20-070-06 • CWE-312: Cleartext Storage of Sensitive Information •

CVSS: 6.1EPSS: 0%CPEs: 11EXPL: 0

In Rockwell Automation MicroLogix 1400 Controllers Series A, All Versions Series B, v15.002 and earlier, MicroLogix 1100 Controllers v14.00 and earlier, CompactLogix 5370 L1 controllers v30.014 and earlier, CompactLogix 5370 L2 controllers v30.014 and earlier, CompactLogix 5370 L3 controllers (includes CompactLogix GuardLogix controllers) v30.014 and earlier, an open redirect vulnerability could allow a remote unauthenticated attacker to input a malicious link to redirect users to a malicious site that could run or download arbitrary malware on the user’s machine. En los controladores Microwell® 1400 de Rockwell Automation serie A, todas las versiones serie B, v15.002 y anteriores, controladores MicroLogix 1100 v14.00 y anteriores, controladores CompactLogix 5370 L1 v30.014 y anteriores, controladores CompactLogix 5370 L2 v30.014 y anteriores, CompactLogix Controladores 5370 L3 (incluye controladores CompactLogix GuardLogix) v30.014 y anteriores, una vulnerabilidad de redireccionamiento abierto podría permitir que un atacante remoto no autenticado ingrese un enlace malicioso para redirigir a los usuarios a un sitio malicioso que podría ejecutar o descargar malware arbitrario en la máquina del usuario. • https://ics-cert.us-cert.gov/advisories/ICSA-19-113-01 https://www.securityfocus.com/bid/108049 • CWE-601: URL Redirection to Untrusted Site ('Open Redirect') •