Page 2 of 9 results (0.002 seconds)

CVSS: 9.8EPSS: 0%CPEs: 22EXPL: 0

A Weak Password Requirements issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 programmable-logic controllers 1763-L16AWA, Series A and B, Version 16.00 and prior versions; 1763-L16BBB, Series A and B, Version 16.00 and prior versions; 1763-L16BWA, Series A and B, Version 16.00 and prior versions; and 1763-L16DWD, Series A and B, Version 16.00 and prior versions and Allen-Bradley MicroLogix 1400 programmable logic controllers 1766-L32AWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWAA, Series A and B, Version 16.00 and prior versions; 1766-L32BXB, Series A and B, Version 16.00 and prior versions; 1766-L32BXBA, Series A and B, Version 16.00 and prior versions; and 1766-L32AWAA, Series A and B, Version 16.00 and prior versions. The affected products use a numeric password with a small maximum character size for the password. Se detectó un problema de Requisitos de Contraseña Débiles en los controladores lógicos programables MicroLogix 1100 1763-L16AWA, Series A y B, versión 16.00 y anteriores; 1763-L16BBB, Serie A y B, versión 16.00 y anteriores; 1763-L16BWA, Serie A y B, versión 16.00 y anteriores; y 1763-L16DWD, Series A y B, versión 16.00 y anteriores de Allen-Bradley en Rockwell Automation y controladores lógicos programables MicroLogix 1400 1766-L32AWA, Series A y B, versión 16.00 y anteriores; 1766-L32BWA, Serie A y B, versión 16.00 y anteriores; 1766-L32BWAA, Serie A y B, versión 16.00 y anteriores; 1766-L32BXB, Serie A y B, versión 16.00 y anteriores; 1766-L32BXBA, Serie A y B, versión 16.00 y anteriores; y 1766-L32AWAA, Series A y B, versión 16.00 y anteriores de Allen-Bradley en Rockwell Automation. Los productos afectados usan una contraseña numérica con un pequeño tamaño máximo de caracteres para la contraseña. • http://www.securitytracker.com/id/1038546 https://ics-cert.us-cert.gov/advisories/ICSA-17-115-04 • CWE-326: Inadequate Encryption Strength CWE-521: Weak Password Requirements •

CVSS: 4.0EPSS: 0%CPEs: 20EXPL: 0

An issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 controller 1763-L16AWA, Series A and B, Version 14.000 and prior versions; 1763-L16BBB, Series A and B, Version 14.000 and prior versions; 1763-L16BWA, Series A and B, Version 14.000 and prior versions; and 1763-L16DWD, Series A and B, Version 14.000 and prior versions. Because of an Incorrect Permission Assignment for Critical Resource, users with administrator privileges may be able to remove all administrative users requiring a factory reset to restore ancillary web server function. Exploitation of this vulnerability will still allow the affected device to function in its capacity as a controller. Ha sido descubierto un problema en controlador Rockwell Automation Allen-Bradley MicroLogix 1100, 1763-L16AWA, Serie A y B, Versión 14.000 y versiones anteriores; 1763-L16BBB, Serie A y B, Versión 14.000 y versiones anteriores; 1763-L16BWA, Serie A y B, Versión 14.000 y versiones anteriores; y 1763-L16DWD, Serie A y B, Versión 14.000 y versiones anteriores. Debido a una asignación de permisos incorrecta para recursos críticos, los usuarios con privilegios de administrador pueden eliminar todos los usuarios administrativos requiriéndose un restablecimiento de fábrica para restaurar la función del servidor web auxiliar. • http://www.securityfocus.com/bid/95302 https://ics-cert.us-cert.gov/advisories/ICSA-16-336-06 •

CVSS: 7.3EPSS: 0%CPEs: 20EXPL: 0

An issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 controller 1763-L16AWA, Series A and B, Version 14.000 and prior versions; 1763-L16BBB, Series A and B, Version 14.000 and prior versions; 1763-L16BWA, Series A and B, Version 14.000 and prior versions; and 1763-L16DWD, Series A and B, Version 14.000 and prior versions. User credentials are sent to the web server in clear text, which may allow an attacker to discover the credentials if they are able to observe traffic between the web browser and the server. Ha sido descubierto un problema en controlador Rockwell Automation Allen-Bradley MicroLogix 1100, 1763-L16AWA, 1763-L16AWA, Series A y B, Versión 14.000 y versiones anteriores; 1763-L16BBB, Series A y B, Versión 14.000 y versiones anteriores; 1763-L16BWA, Series A y B, Versión 14.000 y versiones anteriores; y 1763-L16DWD, Series A y B, Versión 14.000 y versiones anteriores. Las credenciales de usuario son enviadas al servidor web en texto plano, lo que puede permitir a un atacante descubrir las credenciales si son capaces de observar el tráfico entre el navegador web y el servidor. • http://www.securityfocus.com/bid/95302 https://ics-cert.us-cert.gov/advisories/ICSA-16-336-06 •

CVSS: 7.5EPSS: 13%CPEs: 6EXPL: 0

Rockwell Automation MicroLogix 1400 PLC 1766-L32BWA, 1766-L32AWA, 1766-L32BXB, 1766-L32BWAA, 1766-L32AWAA, and 1766-L32BXBA devices have a hardcoded SNMP community, which makes it easier for remote attackers to load arbitrary firmware updates by leveraging knowledge of this community. Dispositivos Rockwell Automation MicroLogix 1400 PLC 1766-L32BWA, 1766-L32AWA, 1766-L32BXB, 1766-L32BWAA, 1766-L32AWAA y 1766-L32BXBA tienen una comunidad SNMP codificada, lo que facilita a atacantes remotos cargar actualizaciones de firmware arbitrarias aprovechando el conocimiento de esta comunidad. • http://www.securityfocus.com/bid/92428 https://ics-cert.us-cert.gov/advisories/ICSA-16-224-01 • CWE-284: Improper Access Control •