Page 2 of 9 results (0.006 seconds)

CVSS: 7.5EPSS: 0%CPEs: 2EXPL: 0

A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to decode the password using rainbow table. Existe una vulnerabilidad de permisos, privilegios y control de acceso en el producto Modicon M221, de Schneider Electric (todas las referencias y todas las versiones anteriores al firmware V1.6.2.0). La vulnerabilidad permite que usuarios no autorizados descifren la contraseña mediante tablas rainbow. • http://www.securityfocus.com/bid/105182 https://www.schneider-electric.com/en/download/document/SEVD-2018-235-01 • CWE-862: Missing Authorization •

CVSS: 9.8EPSS: 0%CPEs: 2EXPL: 0

An Information Management Error vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to replay authentication sequences. If an attacker exploits this vulnerability and connects to a Modicon M221, the attacker can upload the original program from the PLC. Existe una vulnerabilidad de error de gestión de información en el producto Modicon M221, de Schneider Electric (todas las referencias y todas las versiones anteriores al firmware V1.6.2.0). La vulnerabilidad permite que usuarios no autorizados reproduzcan secuencias de autenticación. • http://www.securityfocus.com/bid/105182 https://www.schneider-electric.com/en/download/document/SEVD-2018-235-01 • CWE-294: Authentication Bypass by Capture-replay •

CVSS: 7.8EPSS: 0%CPEs: 2EXPL: 0

An Improper Check for Unusual or Exceptional Conditions vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to remotely reboot Modicon M221 using crafted programing protocol frames. Existe una vulnerabilidad de comprobación incorrecta de condiciones inusuales o excepcionales en el producto Modicon M221, de Schneider Electric (todas las referencias y todas las versiones anteriores al firmware V1.6.2.0). La vulnerabilidad permite que usuarios no autorizados reinicien Modicon M221 remotamente mediante frames manipulados del protocolo de programación. • http://www.securityfocus.com/bid/105171 https://ics-cert.us-cert.gov/advisories/ICSA-18-240-02 https://www.schneider-electric.com/en/download/document/SEVD-2018-233-01 • CWE-754: Improper Check for Unusual or Exceptional Conditions •

CVSS: 6.5EPSS: 0%CPEs: 6EXPL: 0

A Predictable Value Range from Previous Values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections. Un problema de Rango de Valor Predecible de Valores Anteriores fue detectado en PLCs Modicon M221, versiones de firmware anteriores a 1.5.0.0, Modicon M241, versiones de firmware anteriores a la 4.0.5.11, y Modicon M251, versiones de firmware anteriores a la 4.0.5.11 de Schneider Electric. Los productos afectados generan números de secuencia inicial TCP de aleatoriedad insuficientemente que pueden permitir a un atacante predecir los números de los valores anteriores. • http://www.securityfocus.com/bid/97254 https://ics-cert.us-cert.gov/advisories/ICSA-17-089-02 • CWE-331: Insufficient Entropy CWE-343: Predictable Value Range from Previous Values •