Page 3 of 20 results (0.003 seconds)

CVSS: 9.8EPSS: 0%CPEs: 5EXPL: 0

Incomplete List of Disallowed Inputs vulnerability in Mitsubishi Electric MC Works64 versions 4.00A (10.95.201.23) to 4.04E (10.95.210.01), ICONICS GENESIS64 versions 10.95.3 to 10.97, ICONICS Hyper Historian versions 10.95.3 to 10.97, ICONICS AnalytiX versions 10.95.3 to 10.97 and ICONICS MobileHMI versions 10.95.3 to 10.97 allows a remote unauthenticated attacker to bypass the authentication of MC Works64, GENESIS64, Hyper Historian, AnalytiX and MobileHMI, and gain unauthorized access to the products, by sending specially crafted WebSocket packets to FrameWorX server, one of the functions of the products. Una vulnerabilidad "Incomplete List of Disallowed Inputs" en Mitsubishi Electric MC Works64 versiones 4.00A (10.95.201.23) a 4.04E (10.95.210.01), ICONICS GENESIS64 versiones 10.95.3 a 10.97, ICONICS Hyper Historian versiones 10.95.3 a 10.97, ICONICS AnalytiX versiones 10.95.3 a 10.97 e ICONICS MobileHMI versiones 10. 95.3 a 10.97 permite a un atacante remoto no autenticado omitir la autenticación de MC Works64, GENESIS64, Hyper Historian, AnalytiX y MobileHMI, y conseguir acceso no autorizado a los productos, mediante el envío de paquetes WebSocket especialmente diseñados al servidor FrameWorX, una de las funciones de los productos • https://jvn.jp/vu/JVNVU95403720/index.html https://www.cisa.gov/uscert/ics/advisories/icsa-22-020-01 https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2021-026_en.pdf •

CVSS: 5.5EPSS: 0%CPEs: 2EXPL: 0

Plaintext Storage of a Password vulnerability in Mitsubishi Electric MC Works64 versions 4.04E (10.95.210.01) and prior and ICONICS GENESIS64 versions 10.90 to 10.97 allows a local authenticated attacker to gain authentication information and to access the database illegally. This is because when configuration information of GridWorX, a database linkage function of GENESIS64 and MC Works64, is exported to a CSV file, the authentication information is saved in plaintext, and an attacker who can access this CSV file can gain the authentication information. Una vulnerabilidad de almacenamiento de texto plano de una contraseña en Mitsubishi Electric MC Works64 versiones 4.04E (10.95.210.01) y anteriores y en ICONICS GENESIS64 versiones 10.90 a 10.97, permite a un atacante local autenticado conseguir información de autenticación y acceder a la base de datos de forma ilegal. Esto es debido a que cuando la información de configuración de GridWorX, una función de enlace de bases de datos de GENESIS64 y MC Works64, es exportada a un archivo CSV, la información de autenticación es guardada en texto plano, y un atacante que pueda acceder a este archivo CSV puede conseguir la información de autenticación • https://jvn.jp/vu/JVNVU95403720/index.html https://us-cert.cisa.gov/ics/advisories/icsa-22-020-01 https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2021-027_en.pdf • CWE-312: Cleartext Storage of Sensitive Information •

CVSS: 5.5EPSS: 0%CPEs: 3EXPL: 0

Buffer Over-read vulnerability in Mitsubishi Electric MC Works64 versions 4.00A (10.95.201.23) to 4.04E (10.95.210.01), ICONICS GENESIS64 versions 10.97 and prior and ICONICS Hyper Historian versions 10.97 and prior allows an attacker to cause a DoS condition in the database server by getting a legitimate user to import a configuration file containing specially crafted stored procedures into GENESIS64 or MC Works64 and execute commands against the database from GENESIS64 or MC Works64. Una vulnerabilidad de lectura excesiva del búfer en Mitsubishi Electric MC Works64 versiones 4.00A (10.95.201.23) a 4.04E (10.95.210.01), en ICONICS GENESIS64 versiones 10.97 y anteriores, y en ICONICS Hyper Historian versiones 10.97 y anteriores, permite a un atacante causar una condición de denegación de servicio en el servidor de la base de datos al hacer que un usuario legítimo importe un archivo de configuración que contenga procedimientos almacenados especialmente diseñados en GENESIS64 o MC Works64 y ejecute comandos contra la base de datos desde GENESIS64 o MC Works64 • https://jvn.jp/vu/JVNVU95403720/index.html https://us-cert.cisa.gov/ics/advisories/icsa-22-020-01 https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2021-028_en.pdf • CWE-125: Out-of-bounds Read •

CVSS: 7.8EPSS: 0%CPEs: 47EXPL: 0

A maliciously crafted DWG file can be used to write beyond the allocated buffer while parsing DWG files. This vulnerability can be exploited to execute arbitrary code Un archivo DWG malicioso puede ser utilizado para escribir más allá del buffer asignado mientras se analizan los archivos DWG. Esta vulnerabilidad puede ser explotada para ejecutar código arbitrario This vulnerability allows remote attackers to execute arbitrary code on affected installations of ICONICS GENESIS64. User interaction is required to exploit this vulnerability in that the target must visit a malicious page or open a malicious file. The specific flaw exists within the parsing of DWG files. The issue results from the lack of proper validation of user-supplied data, which can result in a write past the end of an allocated data structure. • https://www.autodesk.com/trust/security-advisories/adsk-sa-2022-0007 • CWE-787: Out-of-bounds Write •

CVSS: 4.3EPSS: 0%CPEs: 43EXPL: 0

A maliciously crafted DWG file can be forced to read beyond allocated boundaries when parsing the DWG file. This vulnerability can be exploited to execute arbitrary code. Un archivo DWG diseñado maliciosamente puede ser forzado a leer más allá de los límites asignados al analizar el archivo DWG. Esta vulnerabilidad puede ser explotada para ejecutar código arbitrario This vulnerability allows remote attackers to disclose sensitive information on affected installations of ICONICS GENESIS64. User interaction is required to exploit this vulnerability in that the target must visit a malicious page or open a malicious file. The specific flaw exists within the parsing of DWG files. • https://www.autodesk.com/trust/security-advisories/adsk-sa-2021-0004 https://www.zerodayinitiative.com/advisories/ZDI-21-1236 https://www.zerodayinitiative.com/advisories/ZDI-21-1238 https://www.zerodayinitiative.com/advisories/ZDI-22-378 https://www.zerodayinitiative.com/advisories/ZDI-22-473 • CWE-125: Out-of-bounds Read •