Page 5 of 57 results (0.009 seconds)

CVSS: 9.8EPSS: 0%CPEs: 1EXPL: 0

A CWE-190: Integer Overflow or Wraparound vulnerability exists that could cause heap-based buffer overflow, leading to denial of service and potentially remote code execution when an attacker sends multiple specially crafted messages. Affected Product: Interactive Graphical SCADA System Data Server (V15.0.0.22020 and prior) Una CWE-190: Se presenta una vulnerabilidad de Desbordamiento de Enteros o Wraparound que podría causar un desbordamiento del búfer en la región heap de la memoria, conllevando a una denegación de servicio y potencialmente una ejecución de código remota cuando un atacante envía múltiples mensajes especialmente diseñados. Producto afectado: Interactive Graphical SCADA System Data Server (versiones V15.0.0.22020 y anteriores) • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-039-01 • CWE-190: Integer Overflow or Wraparound •

CVSS: 9.8EPSS: 1%CPEs: 1EXPL: 0

A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could result in remote code execution due to missing length check on user supplied data, when a constructed message is received on the network. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21243 and prior) Una CWE-120: Se presenta una vulnerabilidad de Copia del búfer sin Comprobar el Tamaño de la Entrada que podría resultar en una ejecución de código remota debido a una falta de comprobación de la longitud de los datos suministrados por el usuario, cuando es recibido un mensaje construido en la red. Producto afectado: Interactive Graphical SCADA System Data Collector (dc.exe) (versiones V15.0.0.21243 y anteriores) This vulnerability allows remote attackers to execute arbitrary code on affected installations of Schneider Electric IGSS. Authentication is not required to exploit this vulnerability. The specific flaw exists within the processing of TCP traffic by the dc.exe process. The issue results from the lack of proper validation of the length of user-supplied data prior to copying it to a heap-based buffer. • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-285-03 • CWE-120: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') •

CVSS: 9.8EPSS: 1%CPEs: 1EXPL: 0

A CWE-434: Unrestricted Upload of File with Dangerous Type vulnerability exists that could lead to remote code execution through a number of paths, when an attacker, writes arbitrary files to folders in context of the DC module, by sending constructed messages on the network. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21243 and prior) Una CWE-434: Se presenta una vulnerabilidad de Carga no Restringida de Archivos con Tipo Peligroso que podría conllevar a una ejecución de código remota mediante una serie de rutas, cuando un atacante, escribe archivos arbitrarios en carpetas en el contexto del módulo DC, mediante el envío de mensajes construidos en la red. Producto afectado: Interactive Graphical SCADA System Data Collector (dc.exe) (versiones V15.0.0.21243 y anteriores) This vulnerability allows remote attackers to execute arbitrary code on affected installations of Schneider Electric IGSS. Authentication is not required to exploit this vulnerability. The specific flaw exists within the processing of TCP traffic by the dc.exe process. The issue results from the lack of proper validation of user-supplied data, which can allow the upload of arbitrary files. • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-285-03 • CWE-434: Unrestricted Upload of File with Dangerous Type •

CVSS: 9.1EPSS: 0%CPEs: 1EXPL: 0

A CWE-306: Missing Authentication for Critical Function vulnerability exists that could cause deletion of arbitrary files in the context of the user running IGSS due to lack of validation of network messages. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21243 and prior) Una CWE-306: Se presenta una vulnerabilidad de Falta de Autenticación para una Función Crítica que podría causar el borrado de archivos arbitrarios en el contexto del usuario que ejecuta IGSS, debido a una falta de comprobación de los mensajes de red. Producto afectado: Interactive Graphical SCADA System Data Collector (dc.exe) (versiones V15.0.0.21243 y anteriores) This vulnerability allows remote attackers to delete arbitrary files on affected installations of Schneider Electric IGSS. Authentication is not required to exploit this vulnerability. The specific flaw exists within the processing of commands sent to the server. The issue results from the lack of authentication prior to allowing access to functionality. • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-285-03 • CWE-306: Missing Authentication for Critical Function •

CVSS: 7.5EPSS: 2%CPEs: 1EXPL: 0

A CWE-22: Improper Limitation of a Pathname to a Restricted Directory vulnerability exists that could cause disclosure of arbitrary files being read in the context of the user running IGSS, due to missing validation of user supplied data in network messages. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21243 and prior) Una CWE-22: Se presenta una vulnerabilidad de Limitación Inapropiada de un Nombre de Ruta a un Directorio Restringido que podría causar la divulgación de archivos arbitrarios que son leídos en el contexto del usuario que ejecuta IGSS, debido a una falta de comprobación de los datos suministrados por el usuario en los mensajes de red. Producto afectado: Interactive Graphical SCADA System Data Collector (dc.exe) (versiones V15.0.0.21243 y anteriores) This vulnerability allows remote attackers to disclose sensitive information on affected installations of Schneider Electric IGSS. Authentication is not required to exploit this vulnerability. The specific flaw exists within the processing of TCP traffic by the dc.exe process. The issue results from the lack of authentication prior to allowing access to functionality. • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-285-03 • CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') •