CVE-2022-41644 – Delta Industrial Automation InfraSuite Device Master ModifyPrivByID Missing Authentication Privilege Escalation Vulnerability
https://notcve.org/view.php?id=CVE-2022-41644
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior lacks authentication for a function that changes group privileges. An attacker could use this to create a denial-of-service state or escalate their own privileges. Delta Electronics InfraSuite Device Master versiones 00.00.01a y anteriores carecen de autenticación para una función que cambia los privilegios del grupo. Un atacante podría utilizar esto para crear un estado de denegación de servicio o escalar sus propios privilegios. This vulnerability allows remote attackers to escalate privileges or create a denial-of-service condition on affected installations of Delta Industrial Automation InfraSuite Device Master. • https://www.cisa.gov/uscert/ics/advisories/icsa-22-298-07 • CWE-306: Missing Authentication for Critical Function •
CVE-2022-41772 – Delta Industrial Automation InfraSuite Device Master CheckLoadingStartupConfig Directory Traversal Remote Code Execution Vulnerability
https://notcve.org/view.php?id=CVE-2022-41772
Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior mishandle .ZIP archives containing characters used in path traversal. This path traversal could result in remote code execution. Las versiones 00.00.01a y anteriores de Delta Electronics InfraSuite Device Master manejan mal los archivos .ZIP que contienen caracteres utilizados en el Path Traversal. Este Path Traversal podría resultar en la ejecución remota de código. This vulnerability allows remote attackers to execute arbitrary code on affected installations of Delta Industrial Automation InfraSuite Device Master. • https://www.cisa.gov/uscert/ics/advisories/icsa-22-298-07 • CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') •
CVE-2022-41776 – Delta Industrial Automation InfraSuite Device Master WriteConfiguration Authentication Bypass Vulnerability
https://notcve.org/view.php?id=CVE-2022-41776
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior allow unauthenticated users to trigger the WriteConfiguration method, which could allow an attacker to provide new values for user configuration files such as UserListInfo.xml. This could lead to the changing of administrative passwords. Delta Electronics InfraSuite Device Master versiones 00.00.01a y anteriores permiten a usuarios no autenticados activar el método WriteConfiguration, lo que podría permitir a un atacante proporcionar nuevos valores para archivos de configuración de usuario como UserListInfo.xml. Esto podría dar lugar al cambio de contraseñas administrativas. This vulnerability allows remote attackers to bypass authentication on affected installations of Delta Industrial Automation InfraSuite Device Master. • https://www.cisa.gov/uscert/ics/advisories/icsa-22-298-07 • CWE-306: Missing Authentication for Critical Function •
CVE-2022-41779 – Delta Industrial Automation InfraSuite Device Master DeSerializeBinary Deserialization of Untrusted Data Remote Code Execution Vulnerability
https://notcve.org/view.php?id=CVE-2022-41779
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize network packets without proper verification. If the device connects to an attacker-controlled server, the attacker could send maliciously crafted packets that would be deserialized and executed, leading to remote code execution. Delta Electronics InfraSuite Device Master versiones 00.00.01a y anteriores deserializan paquetes de red sin la verificación adecuada. Si el dispositivo se conecta a un servidor controlado por un atacante, éste podría enviar paquetes creados con fines malintencionados que se deserializarían y ejecutarían, lo que provocaría la ejecución remota de código. This vulnerability allows remote attackers to execute arbitrary code on affected installations of Delta Industrial Automation InfraSuite Device Master Device-Monitor. • https://www.cisa.gov/uscert/ics/advisories/icsa-22-298-07 • CWE-502: Deserialization of Untrusted Data •
CVE-2022-41778 – Delta Industrial Automation InfraSuite Device Master Device-Gateway Service Deserialization of Untrusted Data Remote Code Execution Vulnerability
https://notcve.org/view.php?id=CVE-2022-41778
Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize user-supplied data provided through the Device-DataCollect service port without proper verification. An attacker could provide malicious serialized objects to execute arbitrary code upon deserialization. Delta Electronics InfraSuite Device Master versiones 00.00.01a y anteriores deserializan los datos proporcionados por el usuario proporcionados a través del puerto de servicio Device-DataCollect sin la verificación adecuada. Un atacante podría proporcionar objetos serializados maliciosos para ejecutar código arbitrario tras la deserialización. This vulnerability allows remote attackers to execute arbitrary code on affected installations of Delta Industrial Automation InfraSuite Device Master. • https://www.cisa.gov/uscert/ics/advisories/icsa-22-298-07 • CWE-502: Deserialization of Untrusted Data •