CVE-2018-7851
https://notcve.org/view.php?id=CVE-2018-7851
22 May 2019 — CWE-119: Buffer errors vulnerability exists in Modicon M580 with firmware prior to V2.50, Modicon M340 with firmware prior to V3.01, BMxCRA312xx with firmware prior to V2.40, All firmware versions of Modicon Premium and 140CRA312xxx when sending a specially crafted Modbus packet, which could cause a denial of service to the device that would force a restart to restore availability. CWE-119: Existe una vulnerabilidad de errores de búfer en Modicon M580 con firmware anterior a V2.50, Modicon M340 con firmware... • https://www.schneider-electric.com/en/download/document/SEVD-2019-134-10 • CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer •

CVE-2019-6819
https://notcve.org/view.php?id=CVE-2019-6819
22 May 2019 — A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists which could cause a possible Denial of Service when specific Modbus frames are sent to the controller in the products: Modicon M340 - firmware versions prior to V3.01, Modicon M580 - firmware versions prior to V2.80, All firmware versions of Modicon Quantum and Modicon Premium. Una CWE-754: Existe una vulnerabilidad de Comprobación Inapropiada para condiciones inusuales o excepcionales, que podría generar una posible Denega... • http://www.securityfocus.com/bid/109004 • CWE-754: Improper Check for Unusual or Exceptional Conditions •

CVE-2018-7242
https://notcve.org/view.php?id=CVE-2018-7242
18 Apr 2018 — Vulnerable hash algorithms exists in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. The algorithm used to encrypt the password is vulnerable to hash collision attacks. Existen algoritmos de hash vulnerables en los controladores Modicon Premium, Modicon Quantum, Modicon M340 y BMXNOR0200, de Schneider Electric, en todas las versiones de los módulos de comunicación. El algoritmo empleado para cifrar la contraseña es... • http://www.securityfocus.com/bid/103543 • CWE-326: Inadequate Encryption Strength •

CVE-2018-7761
https://notcve.org/view.php?id=CVE-2018-7761
18 Apr 2018 — A vulnerability exists in the HTTP request parser in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow arbitrary code execution. Existe una vulnerabilidad en Modicon M340, Modicon Premium, Modicon Quantum PLC y BMXNOR0200, de Schneider Electric, que podría permitir la ejecución de código arbitrario. • https://www.schneider-electric.com/en/download/document/SEVD-2018-081-02 • CWE-20: Improper Input Validation •

CVE-2018-7762
https://notcve.org/view.php?id=CVE-2018-7762
18 Apr 2018 — A vulnerability exists in the web services to process SOAP requests in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow result in a buffer overflow. Existe una vulnerabilidad en los servicios web que procesan peticiones SOAP en Modicon M340, Modicon Premium, Modicon Quantum PLC y BMXNOR0200, de Schneider Electric, que podría conducir a un desbordamiento de búfer. • https://www.schneider-electric.com/en/download/document/SEVD-2018-081-02 • CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer •

CVE-2018-7759
https://notcve.org/view.php?id=CVE-2018-7759
18 Apr 2018 — A buffer overflow vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. The buffer overflow vulnerability is caused by the length of the source string specified (instead of the buffer size) as the number of bytes to be copied. Existe una vulnerabilidad de desbordamiento de búfer en Modicon M340, Modicon Premium, Modicon Quantum PLC y BMXNOR0200, de Schneider Electric. La vulnerabilidad de desbordamiento de búfer se provoca por el tamaño de la cadena de ... • https://www.schneider-electric.com/en/download/document/SEVD-2018-081-02 • CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer •

CVE-2018-7760
https://notcve.org/view.php?id=CVE-2018-7760
18 Apr 2018 — An authorization bypass vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. Requests to CGI functions allow malicious users to bypass authorization. Existe una vulnerabilidad de omisión de autenticación en Modicon M340, Modicon Premium, Modicon Quantum PLC y BMXNOR0200, de Schneider Electric. Las peticiones a funciones CGI permiten que usuarios maliciosos omitan la autorización. • https://www.schneider-electric.com/en/download/document/SEVD-2018-081-02 • CWE-287: Improper Authentication •

CVE-2018-7241
https://notcve.org/view.php?id=CVE-2018-7241
18 Apr 2018 — Hard coded accounts exist in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. Existen cuentas embebidas en los controladores Modicon Premium, Modicon Quantum, Modicon M340 y BMXNOR0200, de Schneider Electric, en todas las versiones de los módulos de comunicación. • http://www.securityfocus.com/bid/103542 • CWE-798: Use of Hard-coded Credentials •