Page 12 of 79 results (0.005 seconds)

CVSS: 7.5EPSS: 0%CPEs: 38EXPL: 0

Improper Input Validation vulnerability in Hitachi ABB Power Grids Relion 670 Series, Relion 670/650 Series, Relion 670/650/SAM600-IO, Relion 650, REB500, RTU500 Series, FOX615 (TEGO1), MSM, GMS600, PWC600 allows an attacker with access to the IEC 61850 network with knowledge of how to reproduce the attack, as well as the IP addresses of the different IEC 61850 access points (of IEDs/products), to force the device to reboot, which renders the device inoperable for approximately 60 seconds. This vulnerability affects only products with IEC 61850 interfaces. This issue affects: Hitachi ABB Power Grids Relion 670 Series 1.1; 1.2.3 versions prior to 1.2.3.20; 2.0 versions prior to 2.0.0.13; 2.1; 2.2.2 versions prior to 2.2.2.3; 2.2.3 versions prior to 2.2.3.2. Hitachi ABB Power Grids Relion 670/650 Series 2.2.0 versions prior to 2.2.0.13. Hitachi ABB Power Grids Relion 670/650/SAM600-IO 2.2.1 versions prior to 2.2.1.6. • https://search.abb.com/library/Download.aspx?DocumentID=9AKK107991A8932&LanguageCode=en&DocumentPartId=&Action=Launch https://search.abb.com/library/Download.aspx?DocumentID=9AKK107991A8934&LanguageCode=en&DocumentPartId=&Action=Launch https://search.abb.com/library/Download.aspx?DocumentID=9AKK107991A8936&LanguageCode=en&DocumentPartId=&Action=Launch https://search.abb.com/library/Download.aspx?DocumentID=9AKK107991A8937&LanguageCode=en&DocumentPartId=&Action=Launch https://search.abb.com/library/Download.aspx? • CWE-20: Improper Input Validation •

CVSS: 9.8EPSS: 17%CPEs: 3EXPL: 0

ABB MicroSCADA Pro SYS600 version 9.3 suffers from an instance of CWE-306: Missing Authentication for Critical Function. ABB MicroSCADA Pro SYS600 versión 9.3, sufre de una instancia CWE-306: Falta de Autenticación para una Función Crítica. • https://www.rapid7.com/db/modules/exploit/windows/scada/abb_wserver_exec • CWE-306: Missing Authentication for Critical Function •

CVSS: 6.3EPSS: 0%CPEs: 1EXPL: 0

For ABB eSOMS versions 4.0 to 6.0.2, the X-XSS-Protection HTTP response header is not set in responses from the web server. For older web browser not supporting Content Security Policy, this might increase the risk of Cross Site Scripting. Para ABB eSOMS versiones 4.0 hasta 6.0.2, el encabezado de respuesta HTTP X-XSS-Protection no está configurado en las respuestas del servidor web. Para navegadores web más antiguos no compatibles con la Política de Seguridad de Contenido, esto podría aumentar el riesgo de ataques de tipo Cross Site Scripting. • https://search.abb.com/library/Download.aspx?DocumentID=9AKK107492A9964&LanguageCode=en&DocumentPartId=&Action=Launch • CWE-16: Configuration CWE-79: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') •

CVSS: 6.5EPSS: 0%CPEs: 1EXPL: 0

For ABB eSOMS versions 4.0 to 6.0.2, the X-Frame-Options header is not configured in HTTP response. This can potentially allow 'ClickJacking' attacks where an attacker can frame parts of the application on a malicious web site, revealing sensitive user information such as authentication credentials. Para ABB eSOMS versiones 4.0 hasta 6.0.2, el encabezado X-Frame-Options no está configurado en la respuesta HTTP. Esto puede permitir potencialmente ataques de tipo "ClickJacking" donde un atacante puede enmarcar partes de la aplicación en un sitio web malicioso, revelando información confidencial del usuario, tales como credenciales de autenticación. • https://search.abb.com/library/Download.aspx?DocumentID=9AKK107492A9964&LanguageCode=en&DocumentPartId=&Action=Launch • CWE-16: Configuration CWE-1021: Improper Restriction of Rendered UI Layers or Frames •

CVSS: 6.5EPSS: 0%CPEs: 1EXPL: 0

For ABB eSOMS 4.0 to 6.0.3, the Cache-Control and Pragma HTTP header(s) have not been properly configured within the application response. This can potentially allow browsers and proxies to cache sensitive information. Para ABB eSOMS versiones 4.0 hasta 6.0.3, los encabezados Cache-Control y Pragma HTTP no han sido configurados apropiadamente dentro de la respuesta de la aplicación. Esto puede permitir potencialmente a navegadores y servidores proxy almacenar en caché información confidencial. • https://search.abb.com/library/Download.aspx?DocumentID=9AKK107492A9964&LanguageCode=en&DocumentPartId=&Action=Launch • CWE-16: Configuration CWE-200: Exposure of Sensitive Information to an Unauthorized Actor CWE-202: Exposure of Sensitive Information Through Data Queries •