Page 16 of 763 results (0.002 seconds)

CVSS: 9.8EPSS: 0%CPEs: 12EXPL: 0

A CWE-306: Missing Authentication for Critical Function vulnerability exists that could allow changes to administrative credentials, leading to potential remote code execution without requiring prior authentication on the Java RMI interface. This vulnerability allows remote attackers to bypass authentication on affected installations of Schneider Electric APC Easy UPS Online. Authentication is not required to exploit this vulnerability. The specific flaw exists within the updateManagerPassword function. The issue results from the exposure of a dangerous function. An attacker can leverage this vulnerability to bypass authentication on the system. • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-101-04&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2023-101-04.pdf • CWE-306: Missing Authentication for Critical Function •

CVSS: 6.5EPSS: 0%CPEs: 3EXPL: 0

A CWE-306: Missing Authentication for Critical Function vulnerability exists in the Data Server TCP interface that could allow deletion of reports from the IGSS project report directory, this would lead to loss of data when an attacker abuses this functionality. Affected Products: IGSS Data Server(IGSSdataServer.exe)(V16.0.0.23040 and prior), IGSS Dashboard(DashBoard.exe)(V16.0.0.23040 and prior), Custom Reports(RMS16.dll)(V16.0.0.23040 and prior). This vulnerability allows remote attackers to delete application-level data on affected installations of Schneider Electric IGSS. Authentication is not required to exploit this vulnerability. The specific flaw exists within the IGSSdataServer process, which listens on TCP port 12401 by default. The issue results from the exposure of a dangerous function. • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-073-04&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2023-073-04.pdf • CWE-306: Missing Authentication for Critical Function •

CVSS: 6.5EPSS: 0%CPEs: 3EXPL: 0

A CWE-345: Insufficient Verification of Data Authenticity vulnerability exists in the Data Server that could allow the renaming of files in the IGSS project report directory, this could lead to denial of service when an attacker sends specific crafted messages to the Data Server TCP port. Affected Products: IGSS Data Server(IGSSdataServer.exe)(V16.0.0.23040 and prior), IGSS Dashboard(DashBoard.exe)(V16.0.0.23040 and prior), Custom Reports(RMS16.dll)(V16.0.0.23040 and prior). This vulnerability allows remote attackers to create a denial-of-service condition on affected installations of Schneider Electric IGSS. Authentication is not required to exploit this vulnerability. The specific flaw exists within the IGSSdataServer process, which listens on TCP port 12401 by default. The issue results from the exposure of a dangerous function. • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-073-04&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2023-073-04.pdf • CWE-345: Insufficient Verification of Data Authenticity •

CVSS: 7.8EPSS: 0%CPEs: 3EXPL: 0

A CWE-502: Deserialization of Untrusted Data vulnerability exists in the Dashboard module that could cause an interpretation of malicious payload data, potentially leading to remote code execution when an attacker gets the user to open a malicious file. Affected Products: IGSS Data Server(IGSSdataServer.exe)(V16.0.0.23040 and prior), IGSS Dashboard(DashBoard.exe)(V16.0.0.23040 and prior), Custom Reports(RMS16.dll)(V16.0.0.23040 and prior). This vulnerability allows remote attackers to execute arbitrary code on affected installations of Schneider Electric IGSS. User interaction is required to exploit this vulnerability in that the target must visit a malicious page or open a malicious file. The specific flaw exists within the DashFiles class. The issue results from the lack of proper validation of user-supplied data, which can result in deserialization of untrusted data. • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-073-04&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2023-073-04.pdf • CWE-502: Deserialization of Untrusted Data •

CVSS: 8.8EPSS: 0%CPEs: 3EXPL: 0

A CWE-306: Missing Authentication for Critical Function vulnerability exists in the Data Server TCP interface that could allow the creation of a malicious report file in the IGSS project report directory, this could lead to remote code execution when a victim eventually opens the report. Affected Products: IGSS Data Server(IGSSdataServer.exe)(V16.0.0.23040 and prior), IGSS Dashboard(DashBoard.exe)(V16.0.0.23040 and prior), Custom Reports(RMS16.dll)(V16.0.0.23040 and prior) This vulnerability allows remote attackers to execute arbitrary code on affected installations of Schneider Electric IGSS. Authentication is not required to exploit this vulnerability. The specific flaw exists within the IGSSdataServer process, which listens on TCP port 12401 by default. The issue results from the exposure of a dangerous function. An attacker can leverage this in conjunction with other vulnerabilities to execute arbitrary code in the context of the current user. • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-073-04&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2023-073-04.pdf • CWE-306: Missing Authentication for Critical Function •