CVE-2022-4062
https://notcve.org/view.php?id=CVE-2022-4062
A CWE-285: Improper Authorization vulnerability exists that could cause unauthorized access to certain software functions when an attacker gets access to localhost interface of the EcoStruxure Power Commission application. Affected Products: EcoStruxure Power Commission (Versions prior to V2.25) • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-347-03&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2022-347-03_EcoStruxure_Power_Commission_Security_Notification.pdf • CWE-285: Improper Authorization •
CVE-2021-22786
https://notcve.org/view.php?id=CVE-2021-22786
A CWE-200: Information Exposure vulnerability exists that could cause the exposure of sensitive information stored on the memory of the controller when communicating over the Modbus TCP protocol. Affected Products: Modicon M340 CPU (part numbers BMXP34*) (Versions prior to V3.30), Modicon M580 CPU (part numbers BMEP* and BMEH*) (Versions prior to SV3.20), Modicon MC80 (BMKC80) (Versions prior to V1.6), Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S) (All Versions), Modicon Momentum MDI (171CBU*) (Versions prior to V2.3), Legacy Modicon Quantum (All Versions) • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-221-04&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2022-221-04-Modicon_Controllers_Ethernet_Modules_Security_Notification.pdf • CWE-200: Exposure of Sensitive Information to an Unauthorized Actor •
CVE-2022-24324
https://notcve.org/view.php?id=CVE-2022-24324
A CWE-120: Buffer Copy without Checking Size of Input vulnerability exists that could cause a stack-based buffer overflow potentially leading to remote code execution when an attacker sends a specially crafted message. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22073) • https://download.schneider-electric.com/files?p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2022-102-01_IGSS_Security_Notification_V2.0.pdf • CWE-120: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') •
CVE-2023-22611
https://notcve.org/view.php?id=CVE-2023-22611
A CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exists that could cause information disclosure when specific messages are sent to the server over the database server TCP port. Affected Products: EcoStruxure Geo SCADA Expert 2019 - 2021 (formerly known as ClearSCADA) (Versions prior to October 2022) Existe una vulnerabilidad CWE-200: Exposición de información confidencial a un actor no autorizado que podría provocar la divulgación de información cuando se envían mensajes específicos al servidor a través del puerto TCP del servidor de la base de datos. Productos afectados: EcoStruxure Geo SCADA Expert 2019 - 2021 (anteriormente conocido como ClearSCADA) (Versiones anteriores a octubre de 2022) • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-010-02&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2023-010-02_Geo_SCADA_Security_Notification.pdf • CWE-200: Exposure of Sensitive Information to an Unauthorized Actor •
CVE-2023-22610
https://notcve.org/view.php?id=CVE-2023-22610
A CWE-863: Incorrect Authorization vulnerability exists that could cause Denial of Service against the Geo SCADA server when specific messages are sent to the server over the database server TCP port. • https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2023-010-02&p_enDocType=Security+and+Safety+Notice&p_File_Name=SEVD-2023-010-02_Geo_SCADA_Security_Notification.pdf • CWE-863: Incorrect Authorization •